Delta Electronics VFD S 115V Series User Manual page 61

Compact low-cost easy-to-use general-purpose ac motor drives
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-S Series
Pr.
Source of Master Frequency
2-00
Command
Source of Operation
2-01
Command
2-02
Stop Method
2-03
PWM Carrier Frequency Selections
2-04
Motor Direction Control
2-05
Loss of ACI Signal
2-06
Analog Auxiliary Frequency Operation
5-4
Explanation
Settings
d3: Master Frequency determined
by Potentiometer on the digital
keypad. (won't record the
frequency of power loss and it
can do analog overlap plus)
d4: Master Frequency operated by
RS-485 serial communication
interface and record frequency
of power loss. (record the
frequency of power loss and it
can do analog overlap plus)
d5: Master Frequency operated by
RS-485 serial communication
interface and won't record
frequency before power loss.
(won't record the frequency of
power loss and it can do analog
overlap plus)
d0: Digital Keypad
d1: External terminals. Keypad
STOP/RESET enabled.
d2: External terminals. Keypad
STOP/RESET disabled.
d3: RS-485 serial communication
(RJ-11) .Keypad STOP/RESET
enabled.
d4: RS-485 serial communication
(RJ-11). Keypad STOP/RESET
disabled.
d0: STOP: ramp to stop; E.F.: coast
to stop
d1: STOP: coast to stop; E.F.: coast
to stop
d3: 3KHz
d4: 4KHz
d5: 5KHz
d6: 6KHz
d7: 7KHz
d8: 8KHz
d9: 9KHz
d10: 10KHz
d0: Enable forward/reverse
operation
d1: Disable reverse operation
d0: Decelerate to 0 Hz
d1: Coast to stop and display "EF"
d2: Continue operation by last
frequency command
d0: Disable
d1: Enable + AVI
d2: Enable + ACI
Revision August 2008, SE09, SW V2.61
Factory
NOTE
Setting
d0
d0
d0
d10
d0
d0
d0