Chapter 5 Parameters|VFD-S Series
the setting frequency of parameters, such as Max. operation frequency, 1
they are still needed to set with actual value.
+
Target
Value
If the input range of sensor is 0~SI_max, output range is SO_min~SO_max and then
Input
Per output
Set input range of drive is D_range= 10V(0~10V) or 16mA (4~20mA) that correspond to 0~1-00Hz
Output
Per input
and then
According to the display value of F and H = actual value
=A-13/1-00. If you want the result to be display value = sensor output and actual value = drive output,
A-13
=
1-00
and then
Example:
Sensor: 0~6 psi input corresponds to 0~5V output drive AVI: 0~10V input corresponds to 0~60Hz, A-
01=100
100
A-13 = 6
X
5-0
100
5-78
P
I
A-02
A-03
D
A-04
Detection
Value
Gain
A-01
SI_max
SO_max-SO_min
is
1-00
D_range
will be
SI_max
X
SO_max-SO_min
1-00
D_range
= 12
X
10
+
Integration's
+
Upper
Bound
+
Frequency
A-05
Output Value
A-00
, set drive input to sensor output
A-13/1-00, and then
A-01
100
A-13 =
SO_max-SO_min
st
speed and etc.,
PID Frequency
Output
Command
Limit
A-07
Display value of F, H
Actual value
SI_max
A-01
X
X
100
Revision August 2008, SE09, SW V2.61
One-Time
Delay
A-06
Frequency
Command
D_range