(3) Command code: 10H, write n word, n<=12
For example, writing 6000(1770H) to Pr 5-00 (address 0500H) and1000(03E8H) to Pr 5-
01 (address 0501H) with slave address 01H.
ASCII Mode:
Command message:
ADR 1
ADR 0
Starting Data address
Number of data
(count by word)
Number of data
(count by byte)
Data content of
address 0500H
Data content of
address 0501H
LRC CHK 1
LRC CHK 0
RTU mode:
Command message:
Starting Data address
Number of data
(count by word)
Number of data
(count by Byte)
Data content of
address 0500H
Data content of
address 0501H
CRC CHK Low
CRC CHK High
5-68
STX
':'
'0'
'1'
CMD1
'1'
CMD0
'0'
'0'
'5'
'0'
'0'
'0'
'0'
'0'
'2'
'0'
'4'
'1'
'7'
'7'
'0'
'0'
'3'
'E'
'8'
'7
'2
END1
CR
END0
LF
ADR
01H
CMD
10H
05H
00H
00H
02H
04H
17H
70H
03H
E8H
C8H
2EH
Response message:
STX
ADR 1
ADR 0
CMD1
CMD0
Starting Data
address
Number of data
(count by word)
LRC CHK 1
LRC CHK 0
END1
END0
Response message:
ADR
CMD
Starting Data
address
Number of data
(count by word)
CRC CHK Low
CRC CHK High
Revision August 2008, SE09, SW V2.61
':'
'0'
'1'
'1'
'0'
'0'
'5'
'0'
'0'
'0'
'0'
'0'
'2'
'E'
'8'
CR
LF
01H
10H
05H
00H
00H
02H
41H
04H

Advertisement