Appendix 9.6 Parts for EMC Countermeasures

Appendix 9.6.1 Shield clamp fitting

The effect can be enhanced by directly connecting the outer sheath of the cable to the grounding plate
as shown below.
Install the grounding plate near the outlet (within 10cm) of each panel, and press against the
grounding plate with the clamp fitting. If the cables are thin, several can be bundled and clamped
together.
To provide sufficient frame grounding, install the grounding plate directly on the cabinet or connect
with a grounding wire.
If the grounding plate and clamp fitting set AERSBAN- SET is required, please contact Mitsubishi.
Outline drawing
Grounding plate
2-φ5 hole
Installation hole
Note 1)
M4 screw
AERSBAN-DSET
100
AERSBAN-ESET
APPENDIX 9 EMC INSTALLATION GUIDELINES
Appendix 9.6 Parts for EMC Countermeasures
Clamp fitting
(Fitting A,B)
Clamp section drawing
17.5
6
22
35
Note 1) Screw hole for wiring to cabinet's grounding plate.
Note 2) The grounding plate thickness is 1.6mm.
A
B
C
Enclosed fitting
86
30
Two A clamp fittings
70
56
One B clamp fitting
I - 114
Get other manuals https://www.bkmanuals.com
Peel off the cable sheath at the
clamp section.
Cable
Grounding
plate
Cable
Shield
sheath
Clamp fitting
MAX L
10
Unit: mm
L
A clamp fitting
70
B clamp fitting
45