When checking piping connections for gas leaks, use pre-
ferred means. Kitchen detergents can cause harmful corro-
sion on various metals used in gas piping. Use of a specialty
Gas Leak Detector is strongly recommended. It is available
through Lennox under part number 31B2001. See Corp.
8411−L10, for further details.
Do not use matches, candles, flame or any other source of
ignition to check for gas leaks.
D−Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to
inlet pressure tap (field provided). See figure 22. Check
gas line pressure with unit firing at maximum rate. Low
pressure may result in erratic operation or underfire. High
pressure can result in permanent damage to gas valve or
overfire. For natural gas units, operating pressure at unit
gas connection must be a minimum of 4.5" W.C. For L.P.
gas units, operating pressure at unit gas connection must
be a minimum of 9.0" W.C.
On multiple unit installations, each unit should be checked
separately, with and without other units operating. Supply
pressure must fall within range listed in previous para-
graph.
E−Check Manifold Pressure
After line pressure has been checked and adjusted, check
manifold pressure. Move pressure gauge to outlet pres-
sure tap located on unit gas valve (GV1). Checks of man-
ifold pressure are made as verification of proper regulator
adjustment. Manifold pressure for the 80MGF can be mea-
sured at any time the gas valve is open and is supplying gas
to the unit. Normal manifold pressure for natural gas units is
3.5 in. w.c. For LP/propane gas the correct manifold pres-
sure is 9.0 in. w.c.
IMPORTANT
For safety, connect a shut-off valve between the
manometer and the gas tap to permit shut off of
gas pressure to the manometer.
TABLE 12
GAS VALVE REGULATION
Unit (Fuel)
Operating Pressure (outlet) in. W.C.
Natural
L.P.
3.5 +0 −0.3
9.0 + 0.5
The gas valve is factory set and should not require adjust-
ment. All gas valves are factory regulated. See table 12.
Manifold Adjustment Procedure:
1− Connect a test gauge to outlet pressure tap on gas
valve. Start unit and allow 5 minutes for unit to reach
steady state.
2− While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue. L.P. gas should burn
mostly blue with some orange streaks.
3− After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to values given in
table 12.
NOTE−Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Take care to
replace pressure tap plug.
F− Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check-
ing gas flow. Determine time in seconds for two revolu-
tions of gas through the meter. (Two revolutions assures
a more accurate time.) Divide by two and compare to
time in table 13 below. Adjust manifold pressure on gas
valve to match time needed.
NOTE− To obtain accurate reading, shut off all other
gas appliances connected to meter.
GAS METER CLOCKING CHART
80mgf
g
Unit
1 cu ft
Dial
−45
80
−60
60
−75
48
−100
36
−120
30
−140
25
Natural−1000 btu/cu ft
Page 21
TABLE 13
Seconds for One Revolution
Natural
2 cu ft
1 cu ft
Dial
Dial
160
200
120
150
96
120
72
90
60
75
50
64
LP−2500 btu/cu ft
LP
2 cu ft
DIAL
400
300
240
180
150
128