Typical Operating Characteristics - Lennox 80MGF Series Manual

Hide thumbs Also See for 80MGF Series:
Table of Contents

Advertisement

G−High Altitude Derate
NOTE−In Canada, certification for installation at alti-
tudes over 4500 ft. (1372m) above sea level is the juris-
diction of the local authorities.
80MGF−1 through −8 Models
This unit does not require gas pressure adjustment, or
pressure switch change when operating at elevations of 0
to 7500 ft. (0 to 2248m). Check gas line pressure with unit
firing. The minimum pressure as shown on the nameplate
for natural and propane gases must be maintained. No ori-
fice change is required.
NOTE−This is the only permissible field derate for this
appliance.
80MGF−9, −10 and −11 Models
Table 14 shows manifold pressure settings for installations
at different altitudes. Refer to table 15 for pressure switch
replacement for models at elevations of 4500 feet (1372m)
and greater.
TABLE 14
ALTITUDE
GAS FUEL
feet (m)
0 − 4500
0 4500
(0 − 1372)
Propane/LP
4500 − 5500
4500 5500
(1372 − 1676)
Propane/LP
5500 − 6500
5500 6500
(1676 − 1981)
Propane/LP
6500 7500
6500 − 7500
(1372 − 2286)
Propane/LP
TABLE 15
Unit Model
80MGF−45
80MGF−60
80MGF−75
80MGF−100
80MGF−120
80MGF−140
H−Flame Signal
A microamp DC meter is needed to check the flame signal
on the primary ignition control.
Flame (microamp) signal is an electrical current which
passes from the furnace control through the sensor elec-
trode during unit operation. Current passes from the sen-
sor through the flame to ground to complete a safety cir-
cuit.
To Measure Flame Signal:
1− Place meter in series between furnace control and
sensor wire. Connect the positive (+) lead of meter to
MANIFOLD
PRESSURE
in. W.C. (kPa)
Natural
3.5 (0.87)
9.5 (2.36)
Natural
3.4 (0.86)
9.2 (2.29)
Natural
3.3 (0.82)
8.9 (2.21)
Natural
3.2 (0.80)
8.6 (2.14)
Pressure Switch Part Number
No Change
No Change
88J8001
18L2401
18L2401
No Change
the ignition control sensor connection and the nega-
tive (−) lead of the meter to the sensor wire. See figure
23.
2− Set thermostat for a heating demand and check flame
signal with unit operating. See table 16 for microamp
reading for the various control boards used.
FLAME SIGNAL TEST
D.C. MICROAMP
METER
FLAME
SENSOR
SENSOR
WIRE
CONTROL
Ram
EGC
SureLight
Flame signal may rise above 5 microamps for the first few
seconds after ignition then level off within the range.
Fire and explosion hazard.
These instructions MUST be followed exactly.
Can cause a fire or explosion resulting in property
damage, personal injury or loss of life.
V−TYPICAL OPERATING CHARACTERISTICS
A−Blower Operation and Adjustment
NOTE− The following is a generalized procedure and
does not apply to all thermostat controls.
1− Blower operation is dependent on thermostat control
system.
2− Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower
operates continuously on heating speed. With fan
switch in AUTO position, blower cycles with demand or
runs continuously while heating or cooling circuit cycles.
3− Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is in
OFF position.
B−Temperature Rise
Temperature rise for 80MGF units depends on unit input,
blower speed, blower horsepower and static pressure as
marked on the unit rating plate. The blower speed must be
set for unit operation within the range of AIR TEMP. RISE
°F" listed on the unit rating plate.
Page 22
IGNITION
CON-
TERMINAL
TROL
FIGURE 23
TABLE 16
MICROAMP
DROP OUT
SIGNAL
SIGNAL
t1.0
1.0 to 5.0
v.45
1.0 to 5.0
w.70
v.15
WARNING
SENSE"