Installation; Start Up - Lennox 80MGF Series Manual

Hide thumbs Also See for 80MGF Series:
Table of Contents

Advertisement

SPARK ELECTRODE TO BURNER GAP
BURNER
SPARK
ELECTRODE
SPARK ELECTRODE
FLAME SENSOR TO BURNER GAP
BURNER
FLAME SENSOR
FIGURE 18
WHITE RODGERS 36E SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
FIGURE 19
HONEYWELL VR8205 SERIES GAS VALVE
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
GAS VALVE SHOWN IN OFF POSITION
FIGURE 20
I−Combustion Air Blower Prove
(Pressure) Switch (S64)
80MGF series units are equipped with a combustion air
prove switch located on the vestibule panel. The switch is
connected to the combustion air blower housing by means
of a flexible silicone hose. It monitors air pressure in the
combustion air blower housing.
5/16 in.
(7 mm)
5/16 in.
(7 mm)
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
MANIFOLD
PRESSURE
OUTLET
ON
OFF
The switch is a single-pole single-throw pressure switch
electrically connected to the furnace control. The purpose
of the switch is to prevent burner operation if the combus-
tion air blower is not operating.
COMBUSTION AIR BLOWER
PROVE SWITCH
Normally Open
Closes on Negative Pressure
PROVE
SWITCH
On start-up, the switch senses that the combustion air
blower is operating. It closes a circuit to the furnace control
when pressure inside the combustion air blower increases
above pressure switch set point (In. negative w.c.). The
pressure sensed by the switch is relative to atmospheric
pressure. If the flue becomes obstructed during operation,
the switch senses a loss of negative pressure (pressure
becomes more equal with atmospheric pressure) and
opens the circuit to the furnace control and gas valve. The
switch trip pressure is different depending on unit model
number. The trip pressure is printed on the side of the limit.
The switch is factory set and is not field adjustable. It is a
safety shut-down control in the furnace and must not be
bypassed for any reason.
II−PLACEMENT AND INSTALLATION
Make sure unit is installed in accordance with installation
instructions and applicable does.
III−START-UP
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas
is heavier than air and will settle on the floor.
Use only your hand to turn the gas control knob. Never use
tools. If the knob will not turn by hand, do not try to repair it,
call a qualified service technician. Force or attempted repair
may result in a fire or explosion.
Page 19
PROVE SWITCH
Sensing Tube
Attaches to Top
Side Of Blower
Back
Left
Bottom
FIGURE 21
Top
Right
Front