The AL function is switched off by default. A message containing the date is shown as soon as the AL function
terminates successfully. We recommend to set the „AL start time" in a period where little or no withdrawal of water
takes place.
b
The user has to make sure that the storage temperature is AL Tset +5° when starting AL. When the storage sensor
S3 is installed: If AL Tset+5° is not reached, the AL function is not started.
b
The AL function does not provide total protection against legionella because is not possible to monitor temperatures
throughout the storage cylinder and in all connecting pipes and because the controller is dependent on sufficient
energy being fed in.
5.2 Limescale protection
To prevent the accumulation of limescale, the pump can be set to continue pumping water through the heat exchanger
after a draw-off of between 5 and 30 seconds or until the temperature at the VFS drops below Tset. Settings range: On,
Off / Default: Off.
5.3 Setpoint auto-regulation
This function is used if the primary circuit does not always reach the required temperature.
With this function active:
If no storage sensor is connected:
If setpoint temperature is not reached after 60 seconds, setpoint temperature minus 3 °C is assumed as a new setpoint.
When the primary circuit pump stops, setpoint temperature is returned to the original Tset value.
If a storage sensor is connected:
If the temperature measured by the storage sensor is below Tset - 5 °C, the setpoint is lowered to setpoint minus 5 °C.
In both cases, "Tmin recirculation" is lowered to the new setpoint temperature – recirculation hysteresis minus 5°C, at
which "Tmin recirculation" is no lower than 0°C and no higher than the Tmin recirculation setpoint.
Settings range: On, Off / Default: Off.
5.4 Seizing protection
If seizing protection is active, the controller switches the output in question and the connected components for 5 seconds
every day at 12:00 ("Daily" setting), or every Sunday at 12:00 ("Weekly" setting), in order to prevent the pump and/or the
valve from seizing up after a lengthy idle period.
Settings range: Daily, Weekly, Off / Default: Off.

6. SPECIAL FUNCTIONS

Menu "6. Special functions" is used to set basic values
and expanded functions.
b
With the exception of the clock, all settings must be
entrusted solely to expert service technicians. To
quit the menu, press "esc" or select "Exit special
functions".
b
The numbering of the menu items may change from
one system to another.
6.1 Pump V1
This menu contains the settings for 0-10V or PWM pump control.
b
The power supply for high efficiency pumps using 0-10V / PWM control can be connected to the corresponding
relay (V1 -> R1, R2 ->V2), since the relays are activated and deactivated with the signal.
6.1.1 Pump type
This menu is used to set the type of pump and speed control following the pumps data sheet.
0-10V: Speed control of e.g. High efficency pumps by 0-10V signal.
PWM: Speed control of e.g. High efficency pumps by PWM signal.
6.1.2 Pump
This menu allows the selection of preconfigured profiles for different pumps. In practice, the single settings remain acces-
sible even when a profile has been selected.
6.1.3 Output signal
This menu determines the type of pump in use: solar pumps deliver maximum power with a high control signal, whereas
conversely, heating pumps operate at their maximum power rating when the control signal is at its lowest.
Solar = normal, heating = inverted.
Settings range: normal, inverted / Factory setting: Normal.
6.1.4. PWM off
This signal is deactivated when the pump shuts off (Pumps capable of detecting a cable break require a minimum signal)
Settings range: (Solar:) 0 ...50 % / Default: 0 % -
(Heating:) 50 % ... 100 % / Default: 100 %
6.1.5. PWM on
6.Exit special function
6.1.Pump V1
6.2.Speed pump V1
20
Info