Heat Anticipator Setpoints; Start-Up (Cooling); Prestart Check List; Electric Heat Limit Control Setting - York SUNLINE 2000 BCH 036 Installation Manual

Single package heat pump
Hide thumbs Also See for SUNLINE 2000 BCH 036:
Table of Contents

Advertisement

177820-YIM-A-0506
TABLE 21: ELECTRIC HEAT LIMIT CONTROL
SETTING
VOLTAGE
kW
TEMPERATURE LIMIT SWITCH Open Temp
5
7
10
230-1-60
15
1,2,3,4,5
20
30
1,2,3,4,5,6
5
7
10
230-3-60
15
20
1,2,3,4,5,6
30
7
10
460-3-60
15
20
30
10
15
575-3-60
20
30

HEAT ANTICIPATOR SETPOINTS

It is important that the anticipator setpoint be correct.
Too high of a setting will result in longer heat cycles
and a greater temperature swing in the conditioned
space. Reducing the value below the correct setpoint
will give shorter "ON" cycles and may result in the low-
ering of the temperature within the conditioned space.
Refer to Table 22 for the required electric heat anticipa-
tor setting.
Unitary Products Group
º
F
1
140
1,3
140
1,2,3
140
2,4,6
140
140
6
150
150
1,2,3
140
1,2,3
140
1,2,3
150
2,4,6
140
150
1,3,5
160
2,4,6
150
2,4,6
140
2,4,6
140
2,4,6
140
3
160
3
150
2,4,6
140
2,4,6
140
5
160
5
150
Get other manuals https://www.bkmanuals.com
TABLE 22: ELECTRIC HEAT ANTICIPATOR
SETPOINTS
HEATER
VOLTAGE
KW
5
7
10
230-3-60
15
20
30
7
10
15
460-3-60
20
30
10
15
575-3-60
20
30

START-UP (COOLING)

PRESTART CHECK LIST

After installation has been completed:
1. Check the electrical supply voltage being supplied.
Be sure that it is the same as listed on the unit
nameplate.
2. Set the room thermostat to the off position.
3. Turn unit electrical power on.
4. Set the room thermostat fan switch to on.
5. Check indoor blower rotation.
If blower rotation is in the wrong direction.
Refer to Phasing Section in general informa-
tion section.
Check blower drive belt tension.
6. Check the unit supply air (CFM). See "CHECKING
SUPPLY AIR CFM" on page 26.
SETTING, AMPS
TH1
TH2
0.024
0.35
0.024
0.35
0.024
0.35
0.024
0.35
0.024
0.35
0.024
0.35
0.024
0.35
0.024
0.35
0.024
0.35
0.024
0.37
0.024
0.37
0.024
0.35
0.024
0.35
0.024
0.37
0.024
0.37
31