INSTALLATION INSTRUCTION

GENERAL
YORK Model B1HH units are factory assembled heat pumps
designed for outdoor installation on a roof top or a slab. Field-in-
stalled electric heater accessories are available to provide supple-
mental electric heat combined with electric cooling and heating.
The units are completely assembled on rigid, removable base
rails. All piping, refrigerant charge, and electrical wiring is
factory installed and tested. The units require only electric
power and duct connections at the point of installation.
The electric heaters have nickel-chrome resistance wire ele-
ments and utilize single point power connection.
INSPECTION
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier's freight bill. A separate
request for inspection by the carrier's agent should be made in
writing. Refer to Form 50.15-NM for additional information.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING . Notes are intended to clarify or make
the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury
and/or equipment damage may result if installation procedure is not handled properly.
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS
AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELEC-
TRICAL, AND MECHANICAL CODES
INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE
PERSONAL INJURY, PROPERTY DAMAGE AND/OR DEATH.
DE-ENERGIZE THE ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING TO INSPECT, REPAIR OR PERFORM
MAINTENANCE TO THE UNIT.
®
SINGLE PACKAGE HEAT PUMPS
Supersedes: 511.18-N2Y (498)
MODELS B1HH018 THRU 060
1.5 THRU 5 TON
(12 SEER)
CAUTION
WARNING
WARNING
CHAMPION
SERIES
®
REFERENCE
Additional information on the design, installation, operation and
service of this equipment is available in the following reference
forms:
• 55.70-N1
— General Installation
• 55.70-N2
— Pre-start & Post-start Check List
• 511.26-N1.1V — Electric Heater Accessory
REPLACEMENT PARTS
• Refer to Replacement Parts Manual for complete listing of
replacement parts on this equipment.
All forms referenced in this instruction may be ordered from:
YORK Publications Distribution Center
Standard Register
2101 West Tecumseh Road
Norman, Oklahoma 73069
FAX (877) 379-7920
511.18-N2Y (799)
035-16707-000

Advertisement

Table of Contents
loading

Summary of Contents for York CHAMPION B1HH018

  • Page 1: Installation Instruction

    (12 SEER) GENERAL REFERENCE YORK Model B1HH units are factory assembled heat pumps Additional information on the design, installation, operation and designed for outdoor installation on a roof top or a slab. Field-in- service of this equipment is available in the following reference...
  • Page 2: Installation

    511.18-N2Y PRODUCT NOMENCLATURE PRODUCT CATEGORY VOLTAGE CODE B = Single Package Heat Pumps 06 = 208/230-1-60 (Air Cooled) 25 = 208/230-3-60 46 = 460-3-60 PRODUCT GENERATION 58 = 575-3-60 1 = NEW or Current Design NOMINAL COOLING FACTORY CAPACITY (MBH) INSTALLED ELECTRIC HEAT PRODUCT IDENTIFIER 018 = 18,000 BTUH 042 = 42,000 BTUH...
  • Page 3 511.18-N2Y CLEARANCES CONDENSATE DRAIN All units require certain clearances for proper operation and A condensate trap is required to be installed in the condensate service. Refer to Figure 3 for the clearances required for drain. The plumbing must conform to local codes. Use a sealing combustion, construction, servicing and proper unit operation.
  • Page 4: Power Wiring

    511.18-N2Y CONTROL WIRING UNIT TERMINAL STRIP THERMOSTAT NOTE: ** = Minimum wire size of 18 AWG HEAT ANTICIPATOR wire should be used for all field SHOULD BE SET AT 0.25 installed 24 volt wire. AMPS FOR ALL MODELS. 24 VOLT TRANSFORMER PROGRAMMABLE THERMOSTAT ONLY * = Only required on units with...
  • Page 5 511.18-N2Y TABLE 4 - ELECTRICAL DATA (BASIC UNIT) VOLTAGE SUPPLY MAX. MAX. OUTDOOR LIMITATIONS COMPRESSOR MINIMUM FUSE HACR UNIT MODEL POWER TRANSFORMER BLOWER CIRCUIT SIZE, BREAKER POWER SUPPLY MOTOR, SIZE (VA) MOTOR, AMPACITY SIZE, FACTOR AMPS MIN. MAX. AMPS 208/230-1-60 48.0 12.5 0.96...
  • Page 6 511.18-N2Y TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT) COMPRESSOR ELECTRIC HEAT ACCESSORY SUPPLY COND. MAX. MAX. MINIMUM POWER FUSE HACR BLOWER CIRCUIT TOTAL SUPPLY MOTOR SIZE, BREAKER MODEL NO. MOTOR, AMPACITY AMPS AMPS SIZE 2NH04500506 3.8 / 5.0 * 18.1 / 20.8 35.1 / 38.6...
  • Page 7 511.18-N2Y TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT) (Continued) COMPRESSOR ELECTRIC HEAT ACCESSORY SUPPLY COND. MAX. MAX. MINIMUM POWER FUSE HACR BLOWER CIRCUIT TOTAL SUPPLY MOTOR SIZE, BREAKER MOTOR, MODEL NO. AMPACITY AMPS AMPS SIZE 2NH04501058 10.0*** 19.8...
  • Page 8 511.18-N2Y TABLE 6 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 600 CFM (B1HH018) INDOOR WB TEMPERATURE, °F OUTDOOR TEMPERATURE, °F 13.0 18.7 24.5 30.2 — 12.4 17.8 23.1 28.5 — — — 11.8 16.8 21.8 26.8 — — — —...
  • Page 9 511.18-N2Y TABLE 10 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,000 CFM (B1HH030) INDOOR WB TEMPERATURE, °F OUTDOOR TEMPERATURE, °F — 10.8 15.8 20.8 25.8 30.8 31.7 32.6 33.4 34.3 — 13.6 17.8 22.1 26.3 28.0 29.6 31.3 32.9 —...
  • Page 10 511.18-N2Y TABLE 14 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,400 CFM (B1HH042) INDOOR WB TEMPERATURE, °F OUTDOOR TEMPERATURE, °F 19.6 22.0 24.4 26.8 29.2 31.6 34.0 34.8 35.6 36.4 37.2 19.1 21.5 23.9 26.2 28.6 31.0 33.3 34.2 35.0 35.9 36.7...
  • Page 11 511.18-N2Y TABLE 18 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 2,000 CFM (B1HH060) INDOOR WB TEMPERATURE, °F OUTDOOR TEMPERATURE, °F — — — 15.5 21.2 27.0 32.7 — — — — 14.9 20.6 26.2 31.9 — — — — 14.2 19.9 25.5...
  • Page 12 511.18-N2Y TABLE 20 - SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE 230/460/575 volts EXTERNAL STATIC PRESSURE - IWG 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 MODEL NO. MOTOR SPEED — — — — — — — — —...
  • Page 13 511.18-N2Y TABLE 21 - ADDITIONAL STATIC PRESSURE RESISTANCE RESISTANCE, IWG DISCRIPTION 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000 Wet Indoor coil 0.01 0.01 0.01 0.02 0.01 0.02 0.03 0.04 0.04 0.03 0.04 0.04 0.05 0.05 0.06 0.07 Economizer 0.00...
  • Page 14 511.18-N2Y HIGH VOLTAGE CONN. FRONT ⁄ COMPRESSOR " DIA. KNOCKOUT SERVICE ACCESS HIGH VOLTAGE CONN. COMPARTMENT PANEL ⁄ " DIA. KNOCKOUT DIMENSION LOW VOLTAGE CONN. "A" UNIT SIZE ⁄ “A” “ DIA. KNOCKOUT (OVERALL) ⁄ 018 - 036 33-1/2 042 - 060 41-1/2 SIDE SUPPLY AIR OPENING...
  • Page 15: Sequence Of Operation

    511.18-N2Y SEQUENCE OF OPERATION Anti-short Cycle Timer open and de-energize the indoor blower motor after the appropriate time delay. This unit has an anti-short cycle timer built in to the defrost control. This timer will not permit the compressor to start within Defrost Operation five minutes after the completion of the last cycle or power The minimum time between defrosts can be field selected at...
  • Page 16: Heating Operation

    511.18-N2Y gized. Power is supplied to the compressor and outdoor fan complete, the 24 volt signal energizes contactor coil M1 and motor, and the reversing valve switched to the cooling power is supplied to the compressor and outdoor fan motor. position.
  • Page 17: Normal Maintenance

    511.18-N2Y TABLE 23 - THERMOSTAT SIGNALS (THREE PHASE UNITS) SIGNAL STATE BOARD FUNCTION FAN INSTANT ON "G" FAN INSTANT OFF FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY) REVERSING VALVE ENERGIZED "G" & "Y" & "O" SYSTEM OPERATES IN COOLING COMPRESSOR AND OUTDOOR FAN INSTANT OFF FAN 60 SEC.
  • Page 18: Troubleshooting

    511.18-N2Y TROUBLESHOOTING CAUTION: The wire number or color and terminal designa- WARNING: Troubleshooting of components necessarily re- tions referred to may vary. Check the wiring label quires opening the electrical control box with the inside the control box access panel for the correct power connected to the unit.
  • Page 19: Typical Wiring Diagram Legend

    511.18-N2Y TYPICAL WIRING DIAGRAM LEGEND (See page 18) L E G E N D : C C H C R A N K C A S E H E A T E R ( O P T I O N A L ) C O M P R C O M P R E S S O R D E F R O S T S E N S O R , C L O S E S @...
  • Page 20 511.18-N2Y E L E M E N T A R Y D I A G R A M P O W E R S U P P L Y W I T H P O W E R S U P P L Y W / O U T E L E C H E A T 2 3 0 - 3 - 6 0 E L E C H E A T 2 3 0 - 3 - 6 0 U S E C O P P E R...
  • Page 21 511.18-N2Y TYPICAL WIRING DIAGRAM LEGEND (See page 20) L E G E N D : C I R C U I T B R E A K E R 2 4 V , 3 A M P C C H C R A N K C A S E H E A T E R ( O P T I O N A L ) C O M P R C O M P R E S S O R...
  • Page 22 511.18-N2Y E L E M E N T A R Y D I A G R A M G N D P O W E R S U P P L Y W I T H P O W E R S U P P L Y W / O U T L U G E L E C H E A T 4 6 0 - 3 - 6 0 E L E C H E A T 4 6 0 - 3 - 6 0...
  • Page 23 511.18-N2Y TYPICAL WIRING DIAGRAM LEGEND (See page 22) L E G E N D : C I R C U I T B R E A K E R , 3 A M P C C H C R A N K C A S E H E A T E R C O M P R C O M P R E S S O R D E F R O S T S E N S O R , C L O S E S @...
  • Page 24 511.18-N2Y FIG. 8 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY) Unitary Products Group...
  • Page 25 511.18-N2Y FIG. 9 - TYPICAL WIRING DIAGRAM (230-3-60 POWER SUPPLY) Unitary Products Group...
  • Page 26 511.18-N2Y E L E M E N T A R Y D I A G R A M P O W E R S U P P L Y W / O U T E L E C H E A T 4 6 0 - 3 - 6 0 O R 5 7 5 - 3 - 6 0 G N D U S E C O P P E R...
  • Page 27 511.18-N2Y TYPICAL WIRING DIAGRAM LEGEND (See page 24, 25 and 25) TYPICAL WIRING DIAGRAM NOTES (See page 24, 25 and 25) Unitary Products Group...
  • Page 28 Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A. 511.18-N2Y Copyright  by York International Corporation 1999. All Rights Reserved.

Table of Contents