TABLE 9: ELECTRICAL DATA - BCH036 - 060 DIRECT DRIVE (CONT.)
COMPRESSORS
MODEL
VOLTAGE
RLA
EACH
208-3-60
19.3
230-3-60
19.3
BCH060
460-3-60
10.0
575-3-60
7.9
1.
HACR Type per NEC.
2.
These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
16
ID
OD FAN
BLOWER
LRA
MOTOR
MOTOR
FLA
EACH
FLA
137.0
2.3
6.6
137.0
2.3
6.6
62.0
1.3
3.3
50.0
1.3
3.3
Get other manuals https://www.bkmanuals.com
ELECTRIC HEATER
HEATER
MODEL NO.
KW
None
--
2
2CE04510525
4.0
2
2CE04510725
5.6
2CE04511025
8.0
2CE04511525
11.9
2CE04512025
15.9
2CE04513025
22.2
None
--
2
2CE04510525
5.3
2
2CE04510725
7.5
2CE04511025
10.6
2CE04511525
15.9
2CE04512025
21.2
2CE04513025
29.6
None
--
2
2CE04510746
6.8
2
2CE04511046
10.1
2
2CE04511546
13.6
2
2CE04512046
19.5
2
2CE04513046
28.8
None
--
2CE04511058
10.6
2CE04511558
15.9
2CE04512058
21.2
2CE04513058
30.4
177820-YIM-A-0506
MIN.
MAX. FUSE/
HEATER
CIRCUIT
BRKR
AMPS
AMPACITY
SIZE
(AMPS)
(AMPS)
--
33.0
45
11.1
46.9
60
15.5
52.5
60
22.2
60.8
70
33.0
74.3
80
44.1
88.2
90
61.6
110.1
125
--
33.0
45
12.7
49.0
60
18.0
55.6
70
25.5
64.9
70
38.2
80.8
90
51.0
96.8
100
71.2
122.0
125
--
17.1
25
8.2
27.3
35
12.1
32.3
35
16.4
37.5
40
23.5
46.4
50
34.6
60.4
70
--
13.5
20
10.2
26.2
30
15.3
32.6
35
20.4
39.0
40
29.3
50.1
60