Final check

The air duct kit must be fastened correctly on the air duct by using the supplied three screws (or optional
mounting kit).
The ambient conditions must match the specifications of the components.
The arrow head on the air duct kit must point into the direction of the air flow inside the air duct.
The rubber gasket between the Venturi tube and kit is fitted as required and the tube is fastened with the
appropriate screw in the air duct kit.
The lower end of the Venturi tube is terminated with the supplied end cap (Venturi tubes between 600 mm
and 2800 mm only).
The cabinet must not show any signs of damage. Additional vents into the cabinet are not permitted.
If the air flow against the Venturi tube is present the flow indicator oscillates. The oscillating speed depends
on the air flow speed inside the air duct.
The detector base is mounted in the required position and the corresponding detector is correctly engaged.
The detector base is correctly wired and all terminal screws are tighten.
The filter (Part No. 781444 option) is fitted in required position.
The cover is properly engaged at the fixing points to ensure the IP protection rating.
FB 798349 / 04.13
Venturi-Air Duct Kit
35