Split system single phase type
7.1.12
COMPRESSOR removal
Precautions for exchange of compressor.
Do not allow moisture or debris to get inside refrigerant pipes during work.
Procedure for compressor removal.
1 Turn off the power
2 Remove the TOP PANEL, FRONT PANEL and CABINET RIGHT ASSY.
3 Fully close the 3Way valve (gas) and 3Way valve (liquid)
4 Collect the refrigerant from the 3Way valve.
Start the following work after completely collecting the refrigerant.
Do not reuse the refrigerant that has been collected.
100
WO*A060LDC
WO*A080LDC
Maintenance Document 1589-3