Fujitsu WATERSTAGE WS A050DD6 Series Maintenance Document page 47

Table of Contents

Advertisement

Split system single phase type
COMMAND
ACCESS
LINE
LEVEL
923
S
924
S
928
S
932
S
938
S
941
S
945
S
963
S
1010
U
1012
U
1014
U
1016
S
1020
I
1021
I
1030
I
1040
S
1041
I
1050
I
1060
S
1080
S
1090
S
1091
S
1100
S
1101
S
1130
S
1134
S
1150
I
1151
I
1156
I
1157
I
1200
S
Domestic hot water (with DHW kit or with integrated DHW models)
1610
U
1612
U
1620
I
1640
I
1641
I
1642
I
2056
U
2803
S
2843
S
2844
S
2862
S
2873
S
2882
S
Maintenance Document 1589-3
FUNCTION
Flow temp setp min OT 25°C
Flow temp setp min OT 35°C
Room influence
Room temp limitation
Mixing valve decrease
Actuator running time
Mixing valve in heating mode
With prim contr/system pump
Heating circuit 2
Comfort setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint maximum
Heating curve slope
Heating curve displacement
Summer/winter heating limit
Flow temp setpoint min (for fan
convectors)
Flow temp setpoint max
Room influence
Room temp limitation
Quick setback
Optimum start control max
Optimum stop control max
Reduced setpoint increase start
Reduced setpoint increase end
Mixer valve boost
Actuator running time
Floor curing function
Floor curing setpoint manually
Floor curing day current
Floor curing day completed
Optg mode changeover
Nominal setpoint
Reduced setpoint
Release of DHW load
Legionella function
Legionella function periodically
Legionella function weekday
Swimming pool
Setpoint source heating
Heat pump
Overrun time cond pump
Compressor off time min
Switch-off temp max
Locking time stage 2
Compressor mod run time
Release integr electric flow
SETTING RANGE
6...35°C
18°C
6...35°C
18°C
---/1...100%
80%
---/0...4°C
0.5°C
0...20°C
0°C
30...650s
120s
Open
Control ¦ Open
No
No ¦ Yes
Reduced temp to
20°C
35°C
19°C
4°C to Reduced
8°C
temp
20...35°C
28°C
0,1...4
0,5
-4,5°C...4,5°C
0°C
8°C...30°C
18°C
8°C... 95°C
8°C
8°C... 95°C
55°C
1%...100%
50%
0.5...4°C
0.5°C
Off ¦ Down to reduced
setpoint ¦ Down to frost
Off
prot setpoint
0...360min
180 min
0...360min
30 min
-30...10°C
---
-30...10°C
-5°C
0...50°C
0°C
30...873s
240s
Off
0°C...95°C
25°C
0...32
0...32
0
Protection mode
Thc...65°C
55°C
8°C....Thc
40°C
24h/day
Heating circ time pgms
Time program
Time program 4/DHW
Off-peak rate
4/DHW
4: Time pgm 4/DHW or
Off-peak rate
Off
Off
Periodically
Fixed weekday
1 to 7
7
Mon,...Sun
Sunday
8...80
22
0...240s
240
0...120min
8min
8°C... 100°C
75°C
0...40min
5min
10...240s
240
0... 500°Cmin
100°Cmin
FACTORY
SETTING
47