Fujitsu WATERSTAGE WS A050DD6 Series Maintenance Document page 15

Table of Contents

Advertisement

Split system single phase type
Clear 9: Outdoor temperature thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 4 flashes
Outdoor Unit LED: flash
Probable causes:
Misconnection.
Sensor failure.
Main PCB failure.
Check:
1. Check the sensor connection :
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
-
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature (°C)
Resistance (kΩ)
- If the thermistor is faulty, replace it.
3. Check the electronic board voltage:
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
WO*A060LDC
EXP VALVE
PIPE
DISCHARGE PIPE
OUTDOOR TEMP
- If there is no voltage, replace Main PCB.
Maintenance Document 1589-3
OK
-20
-10
-5
0
115 62,3 46,6 35,2 26,9 20,7 16,1 12,6 7,97 5,18 3,45 2,36 1,65
OK
WO*A080LDC
COMPRESSOR
TEMP
5
10
15
20
COMPRESSOR
TEMP
EXP VALVE
OUTDOOR
TEMP
DISCHARGE
PIPE
PIPE
30
40
50
60
WO*A100LDT
EXP VALVE
COMPRESSOR
TEMP
OUTDOOR
TEMP
PIPE
DISCHARGE
PIPE
70
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Waterstage ws a100dd6 seriesWaterstage wg a050dd6 seriesWaterstage wg a100dd6 seriesWaterstage wo a060ldc seriesWaterstage wo a080ldc seriesWaterstage wo a100ldt series