Download Print this page

Salus CE-HTR230 Installer Manual page 2

Dial thermostat

Advertisement

Contents of the box
5. Thermostat Functions
8. Technical Specification
NSB (Night SetBack) Function
Model:
HTR230
NSB Mode depends on the NSB wired connection.
Voltage:
230 V AC, +-10%, 50/60 Hz
Operating Performance:
230 V: 1,8 W
0V = NSB OFF
Icons used in this manual:
24V= NSB ON
Temperature setback:
2°C-4°C
Temperature range:
5°C- 30°C
The NSB signal is activated every 1 second. When the signal is received the
setpoint temperature will be set at ±2°C or ±4°C.
Span:
+/- 0,5°C
Calibration:
Yes, with jumper
Heating and Cooling Selection
Storage temperature:
-20°C to +60°C
Safety
Ambient temperature:
0 °C up to 45 °C
The Heating/Cooling function is determined by the CO terminal connection.
Degree of protection:
IP 30
CO 0 V = Heat mode
CO 24V= Cool mode
CE conformity according to:
Class II ( EN60730 )
Housing material:
PC, V2
Cooling Blocked function
Color:
RAL 9010 pure white
Important info
Connection:
Screw terminal
Cooling Enabled:
Weight
90g net / 135g gross
Set the jumper on ON
. The thermostat will run in normal cooling mode.
Puls-wide-modulation:
That means that it will open/close the actuators when necessary. The LED will be
Yes
(PWM)
BLUE when the cooling function is running.
HTR230 Thermostat
Valve protection:
Yes
Your benefit
Heating and Cooling:
Yes, automatically Change Over on the CO terminal
Cooling Disabled:
Set the jumper on OFF
. The actuator will be closed and the LED will
Cooling blocked:
Yes, with jumper
be off.
Dimensions:
85mm*85mm*25mm
6. Protection Function
Warranty
Manual Contents:
Heat cut off at high/low temperature:
SALUS Controls warrants that this product (HTR230) will be free from any
When room temperature is over 36°C or under 4°C, all heating/cooling outputs
defect in materials or workmanship, and shall perform in accordance with
will be turned off.
its specification, for a period of five years from the date of installation.
Box Contents
SALUS Controls sole liability for breach of this warranty will be (at its option) to repair
or replace the defective product.
Short cycle protection:
When Cooling Mode is enabled the minimum interval between Relay ON/OFF
Introduction
is 3 minutes.
Customer Name: ......................................................................................................................................................
Valve Protection:
Product Compliance and
Customer Address: .................................................................................................................................................
Set the jumper on ON to disable the function or on OFF to enable it. Turn on the
valve for 5 minutes every week to prevent the valve any damages on the valve.
............................................................................................................................................................................................
Safety Information
....................................................................................... Post Code: ...........................................................................
Sensor Malfunction:
If the temperature sensor or temperature sensor compensation is open the LED
will flash BLUE/RED alternatively.
Tel No: .................................................................... Email: .......................................................................................
Installation
Engineers Company: ..........................................................................................................................................
7. Control Patterns
Fixing Screws
Tel No: ...................................................................... Email: ....................................................................................
User Interface
If CO terminal is connected and the Heating Mode is ON, the PWM function
Instalation Date: ....................................................................................................................................................
will be activated.
Status/LED indication
Engineers Name: ...................................................................................................................................................
If CO terminal is disconnected and the Cooling Mode is ON the ON/OFF control
output will be activated.
Engineers Signature: ...........................................................................................................................................
Installers notes
Warranty
Product Description
Thank you for purchasing the SALUS HTR230 Thermostat. This thermostat is a
device that lets you customise the heating and cooling of your home as needed.
The HTR230 is an electronic room temperature controller which offers key
advantages over conventional mechanical products.
The controller is easy to operate using the conventional backlit adjusting dial
and offers you unique control convenience for heating applications of all types
thanks to the high quality device electronics.
We hope you enjoy our product.
Product Compliance & Safety Information
Product Compliance
SALUS Controls hereby declares that the product complies with the essential
requirements of the following EC Directives: 2014/30/EU, 2014/35/EU and
2011/65/EU. The full text of the EU Declaration of Conformity is available at the
following internet address: www.saluslegal.com.
Safety Information
Use in compliance with safety regulations. The unit is to be used for the control of
room temperature inside the house.
Installation
This accessory must be fitted by a competent person, and installation must
comply with the guidance, standards and regulations applicable to the city,
country or state where the product is installed. Failure to comply with the relevant
standards could lead to prosecution.
Note: All electrical installation work should be carried out by
a suitable qualified electrician or other competent person.
1. Mounting the Thermostat
Install the HTR230 dial room thermostat at roughly 1.5m above floor level. It
should be mounted in a location where the thermostat is easily accessible and
away from direct sunlight.
Dial Thermostat
Model: HTR230
INSTALLER MANUAL
1 x Installer Manual
2. Terminal Connection
Note: You can wire the thermostat
directly to the KL08NSB Wiring
Center (purchased separately).
L
230VAC
50Hz
N
ACTUATOR
Gently remove front housing and
make the wiring connections.
Wall mounting
For wall mounting, mark the correct
possition on the wall and mount the
rear case to the wall.
L
CO
N
25
30ºC
EXTERNAL
E.G.
CLOCK
HEAT
PUMP
L
CO
N
25
30ºC
3. Switching Bridges
Different features of the HTR230
can be switched On or OFF with
the jumpers. In order to do this
please follow the table below.
HTR 230 Switching Bridges
Switch
Feature
VP
Valve protection feature
PWM
Pulse-Width-Modulation
NSB Function (2° or 4°)
Enable
CO
Heating/Cooling
4. Jumpers
The jumpers from 1 to 5 are representing the number of actuators that you can connect
to the thermostat.
After the actuators are mounted please move the jumper on the correct number (the
same as the number of actuators).
Depending on the amount of actuator used, please change the jumper position
accordingly to compensate the power consumption.
ON
OFF
2°C
4°C
Disable

Advertisement

loading

This manual is also suitable for:

Htr230