The optional P.C. board should be connected to the header outdoor unit (U1).
Header outdoor unit
Outdoor unit
interface PCB
ON
OFF
Bit1 OFF, Bit2 ON
6-2-3-2. Power peak-cut Control (Extended)
Operation
The demand request signal from the outside restricts the maximum capability (or maximum electric power)
of an outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch*1
SW2: Power peak-cut control OFF switch*1
*1 The inputs of SW1 and SW2 can be either pulse (100 msec or longer) or step signals.
* Be sure to provide a contact for each terminal.
Extended power peak-cut control settings
[4-stage switching] <SW105 Bit1 ON, Bit2 ON>
Control item
Input demand OFF signal to release the demand
Input demand ON signal to control the demand
Input demand ON signal to control the demand
Input demand ON signal to control the demand
Outdoor unit DN Code (O.DN)
[00E]
0
1
2
3
4
5
6
7
8
9
10
15 (factory default)
(forced stop)
L1: Display lamp ensuring power peak cut control
Optional PCB
Display
relay
[OPERATION]
CN513
PJ17
COM
SW105
ON
COM
1 2 3 4
OFF
Connection cable
Optional P.C.board
Input
SW1
SW2
OFF OFF
ON OFF
OFF ON
ON ON
*The upper limit X%, Y%, Z% can be regulated with the outdoor DN Code (O.DN) [00E] [00F] [010].
Outdoor unit DN Code (O.DN)
X
[00F]
100%
0
95%
1
90%
2
85%
3
80%
4
75%
5
70%
6
65%
7
60%
8 (factory default)
55%
9
50%
10
0%
15
Locally procured
TB1
L1
Shield wire
TB2
[ON]
SW1
[OFF]
SW2
Shield wire
For SW1 and SW2, be sure to provide
no-voltage contacts for each terminal.
Outdoor unit interface P.C.board
Display relay
SW105
Factory default [00E] = 15,
(L1)
Bit1 Bit2
[00F] = 8, [010] = 4
OFF
100% (normal operation) 100% (normal operation)
ON
(upper limit regulated)
OFF ON
ON
(upper limit regulated)
ON
0% (forced stop)
Y
100%
95%
90%
85%
80%
75%
70%
65%
60%
55%
50%
0%
(forced stop)
- 82 -
Power
supply
Demand: power peak-cut control
Outdoor DN Code [∗∗∗]
[00E] = X, [00F] = Y,
[010] = Z
Approx. 80%
Approx. Z% (50% to 100%)
(upper limit regulated)
Approx. 60%
Approx. Y% (50% to 100%)
(upper limit regulated)
Approx. X% (50% to 100%)
(upper limit regulated)
Outdoor unit DN Code (O.DN)
[010]
0
1
2
3
4 (factory default)
5
6
7
8
9
10
15
Z
100%
95%
90%
85%
80%
75%
70%
65%
60%
55%
50%
0%
(forced stop)