▼ (Indoor address)
8
Push the [
] / [
Change Code No. to 13 with [
9
Push the [
] / [
Select the indoor unit address with [
(TU2C-LINK : 0001~0128
TCC-LINK : 0001~0064)
10
Push the "
Fix " [
After "Continue?" is displayed on the screen, push the "
▼ (Group address)
11
Push the [
] / [
Change Code No. to 14 with [
12
Push the [
] / [
Select the group address with [
13
Push the "
Fix " [
After "Continue?" is displayed on the screen, push the "
▼ (Central control address)
14
Push the [
] / [
Change Code No. to 03 with [
15
Push the [
] / [
Select the indoor unit address with [
(TU2C-LINK : 0001~0128
TCC-LINK : 0001~0064)
16
Push the "
Fix " [
After "Continue?" is displayed on the screen, push the "
17
The display changes to "DN setting" , push the "
"
Setting "appears on the display for a while , then the display returns to the " Field setting menu " display.
NOTE
(1) The Code No. [E04] (Indoor / outdoor communication trouble) will appear if line (system) addresses are
mistakenly set.
(2) When manual address setup has been done from a remote controller, and central control over
refrigerant lines is to be done, setup the header unit of each line as follows:
• Using SW101 and SW102 on the interface PC board of the header unit of each line, setup the line
address for each line.
• Turn ON DIP switch 1 of SW100 on the header outdoor unit interface P.C.board of the lowest system
address number.
• After that, set up the central control address. (For central control address setup, refer to the installation
manual of the central control devices.)
] button to select Code No.
] / [
] button.
] button to select Data.
] / [
] button.
Set / Fix] button to set the Data.
] button to select Code No.
] / [
] button.
] button to select Data.
] / [
] button.
Set / Fix] button to set the Data.
] button to select Code No.
] / [
] button.
] button to select Data.
] / [
] button.
Set / Fix ] button to set the Data.
- 116 -
Yes " [
Set / Fix] button.
Yes " [
Set / Fix] button.
No " [
Return] button.
Return" button to finish the settinge operation.