Toshiba MMY-MUP0721HT9P-UL Service Manual page 185

Hide thumbs Also See for MMY-MUP0721HT9P-UL:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Controller
Check
Sub-code
code
1∗: Compressor
1 side
2∗: Compressor
2 side
H01
H01
1∗: Compressor
1 side
H02
H02
2∗: Compressor
2 side
1∗: Compressor
1 side
2∗: Compressor
H03
H03
2 side
H05
H05
H06
H06
H07
H07
Location
Description
System status
of
detection
Compressor
Compressor
All stop
P.C. board
breakdown
Compressor
Compressor
All stop
P.C. board
trouble (lockup)
MG-CTT trouble
Compressor
Current
All stop
P.C. board
detection
circuit trouble
I/F
TD1 sensor
All stop
miswiring
(incomplete
insertion)
I/F
Activation of
All stop
low-pressure
protection
I/F
Low oil level
All stop
protection
- 185 -
Check code detection
Check items (locations)
condition(s)
Inverter current detection
Check power supply
circuit detects overcurrent
voltage. (208-230V ± 10%).
and shuts system down.
Check for failure in
compressor.
• Check for possible cause
of abnormal overloading.
• Check for failure in outdoor
P.C. board (Compressor).
Overcurrent is detected
• Check for failure in
several seconds after
compressor.
startup of inverter
• Check compressor system
compressor.
wiring, particularly for open
phase.
• Check connection of
connectors/terminals on
compressor P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
problem inside
compressor.)
Current flow of at least
• Check current detection
specified magnitude is
circuit wiring.
detected despite inverter
• Check failure in outdoor
compressor having been
P.C. board (Compressor).
shut turned off.
Discharge temperature of
• Check installation of TD1
compressor 1 (TD1) does
sensor.
not increase despite
• Check connection of TD1
compressor being in
sensor connector and
operation.
wiring.
• Check resistance
characteristics of TD1
sensor.
• Check for failure in outdoor
P.C. board (I/F).
Low-pressure Ps sensor
• Check service valves to
detects operating pressure
confirm full opening
lower than 0.02MPa.
(both gas and liquid sides).
• Check outdoor PMVs for
clogging (PMV1, 2, 3).
• Check for failure in SV4
circuits.
• Check for failure in low-
pressure Ps sensor.
• Check indoor filter for
clogging.
• Check valve opening
status of indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor
fan (during heating).
• Check for insufficiency in
refrigerant quantity.
Operating compressor
<All outdoor units in
detects continuous state of
corresponding line to be
low oil level for about 2
checked>
hours.
• Check connection and
installation of TK1 and TK2
sensors.
• Check resistance
characteristics of TK1 and
TK2 sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
problem inside compressor
casing.
• Check SV3D, SV3F valves
for failure.
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing circuit
for clogging.