Check code
Outdoor 7-segment display
Controller
Check
Sub-code
code
1∗: Compressor
1 side
2∗: Compressor
2 side
01: Compressor
1 heat sink
trouble
02: Compressor
2 heat sink
trouble
04: Heat sink
P07
P07
dewing
Detected indoor
address
P10
P10
P11
P12
Location
Description
System status
of
detection
Compressor
Heat sink
All stop
P.C. board
overheating
trouble
I/F
Heat sink
All stop
overheating
trouble
Heat sink
dewing trouble
Indoor unit
Indoor overflow
All stop
trouble
I/F
Outdoor heat
All stop
exchanger
freeze trouble
Indoor unit
Indoor fan
Stop of
motor trouble
corresponding
unit
- 189 -
Check code detection
Check items (locations)
condition(s)
Temperature sensor built
• Check outdoor fan system
into IPM (TH) is overheated.
trouble.
• Check IPM and heat sink for
thermal performance for
failure installation.
(e.g. mounting screws and
thermal conductivity)
• Check for failure in
Compressor P.C. board.
(failure IPM built-in
temperature sensor (TH))
Condensation detection on
• Check outdoor fan system
heat sink has occurred four
trouble.
• Check IPM and heat sink
times or more in operation.
for thermal performance for
Temperature sensor built
troubled installation.
into IPM (TH) is overheated.
(e. g. mounting screws and
thermal conductivity)
• Check for failure in
compressor P.C. board.
(failure IPM built-in
temperature sensor (TH))
• Check shortage of refrigerant.
• Check outdoor service
valves.
• Check connection of TL2
sensor.
• Check resistance
characteristics of TL2 sensor.
• Check resistance
characteristics of TO sensor.
• Check malfunctions of Pd
and Ps sensors.
• Check outdoor I/F P.C.
board malfunction.
• Check PMV2 and PMV3.
• Check refrigerant
stagnation.
• Float switch operates.
• Check float switch
• Float switch circuit is
connector.
open-circuited or
• Check operation of drain
disconnected at connector.
pump.
• Check drain pump circuit.
• Check drain pipe for
clogging.
• Check for failure in indoor
P.C. board.
• Outdoor heat exchanger
• Check shortage of
remaining frost detection
refrigerant.
has occurred eight times
• Check connection of TE1,
or more due to abnormal
TE2 and TE3 sensors.
frost formation in heating
• Check resistance
operation.
characteristics of TE1,
TE2, and TE3 sensors.
• Check disconnection of
TS1 sensor.
• Check resistance
characteristics of TS1
sensor.
• Check outdoor I/F P.C.
board malfunction.
• Check operation of 4 way
valve.
• Check operation of outdoor
PMV (1, 2, 3).
• Check short circuit from
outlet air to inlet air.
• Motor speed
• Check connection of fan
measurements
connector and wiring.
continuously
• Check for failure in fan
deviate from target
motor.
value.
• Check for failure in indoor
• Overcurrent
P.C. board.
protection is
• Check impact of outside air
activated.
treatment (OA).