Fp2 Computer Communications Unit (Ccu) - Omron NV3W Connection Manual

Programmable terminals
Hide thumbs Also See for NV3W:
Table of Contents

Advertisement

FP2 Computer Communications Unit (CCU)

2-6

FP2 Computer Communications Unit (CCU)

PLC Model Selection
Applicable Devices
Bit/word devices
Bit devices
Input relays
Output relays
Internal relays
Link relays
Timers
Counters
Special internal relays
Word devices
Input relays
Output relays
Internal relays
Link relays
Data registers
Link data registers
Timer/counter set value area
Timer/counter elapsed value area
File registers
Special data registers
Note
Communications Settings
Select Panasonic FP Series.
(1) The maximum values that can be set by the PT are given.
(2) The addressable memory ranges depend on the model of PLC that is
used. Refer to the user manuals for your PLC for details.
The following communications settings are recommended for the PT and
PLC.
PT Communications Settings (Set from the NV-Designer using the NV
Configuration.)
Item
Baud rate
Data bits
Stop bits
Parity
PLC Communications Settings
Item
Communications mode
Baud rate
Data bits
Stop bits
Parity
End code
Start code
Unit number
Modem connection
Note With the FP2 CCU, the parity check is always odd and there is al-
ways one stop bit.
No.
X 0000 to X 511F
Y 0000 to Y 511F
R 0000 to R 886F
L 0000 to L 639F
T 0000 to T 3071
C 0000 to C 3071
R 9000 to R 910F
WX 0000 to WX 511
WY 0000 to WY 511
WR 0000 to WR 886
WL 0000 to WL 639
DT 00000 to DT 10239
LD 0000 to LD 8447
SV 0000 to SV 3071
EV 0000 to EV 3071
FL 00000 to FL 32764
DT 90000 to DT 90511
Setting
19,200 bps
8
1
Enabled, odd
Setting
Computer link
19,200 bps
8
1
Enabled, odd
CR
No STX
1
No connection
Section 2-6
Comments
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nv seriesNv3w-v1Nv4wNv3q

Table of Contents