Omron NV3W Connection Manual page 150

Programmable terminals
Hide thumbs Also See for NV3W:
Table of Contents

Advertisement

Modbus Slave (RTU Mode)
Note
128
Connection diagram
RS-485
To power
1:N Connections
supply
PLC
(Modbus-RTU Master)
Signal
+
Terminating resistance
120 Ω
To power
supply
To power
supply
Connect.
Connect the E terminal and -RD terminal at the end node only.
Wire each node to the next node.
Do not branch the wire from one node to more than one other node.
Correct Wiring
Incorrect Wiring
If there is a lot of noise in the environment, implement noise countermea-
sures, such as using shielded cables and attaching ferrite cores. Make sure
that the shield is not exposed, which would make it vulnerable to static elec-
tricity.
The number of nodes, transmission distance, and baud rate will depend on
the devices on the network. Confirm operation using the actual devices.
The maximum transmission distance for 24-V RS-232C for NV-series PTs is 15 m.
The maximum transmission distance for 5-V RS-232C for NV3W (-V1) PTs is 30 m.
The maximum transmission distance for 24-V RS-422A for NV-series PTs is 500 m.
Connection for RS-485 may not be possible depending of the switchover tim-
ing between sending and receiving at the remote device. Confirm operation
using the actual devices.
PT (Modbus-RTU Slave)
Signal
Pin No.
1
+
2
3
NC (or FG)
4
+SD
No.1
−SD
5
6
+RD
−RD
7
E
8
PT (Modbus-RTU Slave)
Signal
Pin No.
1
+
2
3
NC (or FG)
4
+SD
No.2
−SD
5
6
+RD
−RD
7
8
E
PT (Modbus-RTU Slave)
Signal
Pin No.
1
+
2
3
NC (or FG)
+SD
4
No.N
−SD
5
6
+RD
−RD
7
8
E
Section 11-1
PT
NV3W (-V1), NV4W,
or NV3Q for RS-485

Advertisement