.ELECTRICAL WIRING WORK (3/3) )
( Wiring connection method )
Precautions when laying power supply wiring.
• For connection to the terminal block, use ring type crimp style. terminals with insulation
sleeve or treat the wiring with insulation. (Refer to fig. 32)
• I f it is inevitable to use ring type crimp style terminals, make sure to observe the following
items. ( A bnormal heating may occur if the wiring are not tightened securely.)
Connection of 2
wirings of same
must be carried out
on both sides.
• N ever use the stranded wiring which is soldered.
(Slack in the electric wiring may cause abnormal heat.)
• Use the required wirings, connect them securely and fix these wirings so that
external force may not apply to the terminals.
• Use a proper screw driver for tightening the terminal screws.
If an improper screw driver is used, it may damage the screw head and a proper
tightening cannot be carried out.
• If a terminal is over tightened, it may be damaged. Refer to the table shown below
for tightening torque of terminals.
Precautions when connecting the earth terminal
Conduct wiring so that the earth wiring comes out from the
A-..
notched part of the cup washer.
L.11
O therwise, earth wiring contact will be insufficient and earth
C A U TION
effect may be lost.
(specification for field supplied wiring )
For the indoor unit wiring and transmission wiring (broken lines in the drawing),
follow the instructions in the indoor unit's installation manual.
• SPECIFICATIONS OF STANDARD WIRING COMPONENTS
Outdoor Unit
type
RZA125AV16
RZA140AV16
(*) Only in protected piping, use H07RN-F when protected pipes are not used.
(Supply cords shall not be lighter than polychloroprene sheathed flexible cord (code designation 60245 IEC 57))
NOTES
1. Select and install the power supply wiring in accordance with [IEC 60335-1 (Table 11)] or local laws and regulations.
The maximum current of the outdoor and indoor units are shown on each name plate.
2. When installing wiring in a location that can easily come in contact with people, be sure to install an earth
leakage breaker coping with high harmonics to prevent electric shock.
3. Breaker type and capacity shall be selected in accordance with local laws and regulations.
I To the electrician I
• Do not operate the unit until the refrigerant charging is completely.
(If it is operation before that, the compressor will be broken.)
� CAUTION
Connection of 2
wirings on one
0
side is prohibited.
RZA125AV16, RZA140AV16
LN
230V 50Hz
Branch switch,
overcurrent breaker
Indoor Unit
Power supply
Wiring type ( * )
H05VV-U3G
Round crimp-style
terminal
Connection of
""!iring� of different �
sizes 1s
prohibited.
M4 (Wire between units terminal board)
M4 (Power supply terminal board)
M4 (Ground wire between units)
M5 (Ground wire between units)
Ring type crimp-style
terminal
230V 50Hz
POWER SUPPLY
1-
230-240 50/60Hz ----�
230V 50Hz
LN
Q;)
, ,
T
Size
Wiring size and length must
comply with local codes or
[IEC 60335-1 ( T able 11)]
34
X
Electric wire
lnsulaUng sleeve
Fig.13
�,�J
Tightening torque (N•m)
1.50±0.30
1.50±0.30
1.69±0.25
3.55±0.50
Cup washer
Wire type of wiring
between the units
H05VV-U4G2.5