• BEFORE INSTALLATION
• SELECTING INSTALLATION LOCATION (1/2) )
• Install drain piping according to this installation manual to ensure good drainage, and insulate the piping to prevent condensation.
Improper drain piping may cause water leakage, make the furniture get wet.
• Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions or radio to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to eliminate noise.)
• Install the indoor unit as far as possible from fluorescent lamps.
• In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals. Small animals making contact
with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
• Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other parts must be done in accordance with relevant local and national legislation.
• Only qualified personnel can handle, fill, purge and dispose of the refrigerant.
• Do not install the air conditioner in places such as following:
1. Where there is mist of oil, oil spray or vapor for example a kitchen.
Resin parts may deteriorate, and cause them to fall out or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is produced.
Corrosion of copper pipings or brazed parts may cause the refrigerant to leak.
3. Where there is machinery which emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
4. Where flammable gases may leak, where carbon fiber or ignitable dust is suspended
in the air or where volatile flammables, such as thinner or gasoline, are handled. If the
gas should leak and remain around the air conditioner, it may cause ignition.
5. The place that the vibration or the voltage fluctuation give influence.Vehicles, vessels, etc.
The vibration may cause a damage and the voltage fluctuation may cause an abnormal operation.
6. Where small animals may build a nest, fallen leaves are accumulated, or weeds are overgrown.
If small animals touch the electrical parts inside, this may cause malfunction, smoke or a fire .
1 Carefully read these instructions before installation.
• For installation of the indoor unit, refer to the indoor unit installation manual.
I
I
< Transporting Unit >
As shown in the Fig.2, bring the unit slowly.(Take care
not to let hands or things come in contact with rear fins.)
Installation Parts>
<
Always use accessory parts or those
specification as parts required for installation .
(1)
Select the installation location that meets the following conditions and get approval of the customer.
• Places where is no risk of flammable gas leakage.
• Places where the outdoor unit does not bother next-door neighbors.
• Safe places where can withstand the unit's mass and vibration and where the air conditioner can be
installed level.
• Places where are well-ventilated and where servicing space can be well ensured.
The minimum required space is shown in chapter
• Where the piping length between the indoor and the outdoor units is ensured within the
allowable piping length. (Please see chapter@)REFRI G ERANTPI P I N GWORK)
• Do not allow wind from the same direction to blow frequently toward the outlet or inlet of the outdoor
unit. If the wind is likely to blow as mentioned above, make sure to keep
a sufficient service space and install a wind protective shield.
Inverter air conditioners may cause noise to occur in electrical
appliances. As shown in the right drawing, select an installation
site well away from radios, PCs, and stereos.
Especially in the areas where the incoming signal strength is
CAUTION
weak , keep the indoor remote controller 3 meter or more from
electrical appliances. Put the power supply and transmission
wiring in a metal piping and ground the metal piping.
CAUTION
_Lh.
)
<DO NOT THROW AWAY ACCESSORIES
THAT ARE REQUIRED FOR INSTALLATION.>
Outlet side grille
Outdoor unit
Fig.
1
<CAUTION>
of
designated
u
I N STALLATI O N S ERVI C E SPACE)
23

■ Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases
covered by the Kyoto Protocol. Do not vent gases
into the atmosphere.

Refrigerant type: R32

GWPl 1 1 value: 675
< 1 1GWP = global warming potential
• The refrigerant quantity is indicated on the unit
name plate.
When lifting up the unit, do not put
fingers into the inlet hole on the side of
the casing, otherwise the casing may be
deformed.
Work in a team of at least two people when carrying
1.5m or more -- +---,
1m or more
1m ormore
outdoor unit
the
r
Earth leakage
Only Ouct type
breaker
connection
.
I n d00r Unit
� ---- --<-1- _,
>-
0
Fig.2