Downward slo e of at least 1/100
-Lt
CAUTION----------­
If drain stagnates in the drain piping, the piping may be
clogged.
• If sufficient downward inclination cannot be ensured,
carry out upward drain piping.
• Install supports at a distance of 1 to 1.5 m so that the
piping may not deflect.
• Make sure to use the attached drain hose (2) and the
metal clamp (1).
Insert the drain hose (2) into the drain socket up to the
point where the socket diameter becomes larger. Put
the metal clamp (1) to the taped hose end. Be sure to
fasten the screw of the metalclamp (1) until the margin
of the screw thread decreases to 4 mm or less.
Metal clamp (1)
(accessory)
Tape
-Lt
Fig. 11
CAUTION-----------
• Tighten the metal clamp (1) on specified above otherwise.
The drain hose (2), the socket or the metal clamp (1) may
be damaged.
• Wrap the vinyl tape around the end of the metal clamp
(1) so that the sealing material (Large) (5) to be used at
the next process may not be damaged with the clamp
end or bend the tip of the metal clamp (1) inward as
(Refer to Fig. 12)
shown.
Support bracket
Fig. 10
(Refer Fig. 10)
Drain hose (2)
(accessory)
<In case of sticking vinyl tape>
<In case of bending the tip>
Tightened part
Bend the tip without tearing the
sealing material (Large) (5).
< Caution to be taken when carrying out upward drain
piping (Refer to Fig. 13) >
• The maximum height of the drain riser is 467 mm. Since
the drain pump mounted on this indoor unit is a high
head type, from the characteristic point of view, the
higher the drain riser the lower the draining noise.
Therefore, the drain riser of 300 mm or higher is
recommended.
• For upward drain piping, keep the horizontal piping
distance of 300 mm or less between the drain socket
root to the drain riser.
300 or less
t'.: = ======:'.:j ---1 �---1-->,------\--------�
Metal clamp
(accessory)
Drain hose (2)
(accessory)
Keep the drain hose level or make a slight up-grade so_}
that air may not stagnate in the drain hose.
If air stagnates, the drain may flow oppositely when
1
the drain pu
p
tops and gen
_:i
\_
9
l
Stick vinyl tape without
"-
tearing the sealing
material(
r
)(
_
Fig.12
Ceiling slab
Ad"ustable
(467 or less) t:::,
Upward drain piping
(1)
(Field supply)
Drain hose (2)
ra
abnormal s
Fig.13
Vinyl tape
5
)
_
__ _
(unit [mm])
0
g
n
: