Figure 14. Securing an enclosure to a rack cabinet
5. Push the end caps back into position.
6. Repeat this procedure for each additional enclosure that you install.

Step 7. Installing the support rails for file module slides

Review the documentation that comes with the rack cabinet for safety and cabling
information. Before you install the file module in a rack cabinet, review the
following guidelines:
v Two or more people are required to install devices 2U or larger in a rack cabinet.
v Make sure that the room air temperature is below 35°C (95°F).
v Do not block any air vents; usually 15 cm (6 inch) of space provides proper
v Do not leave open spaces above or below an installed file module in the rack
v Install the file module only in a rack cabinet with perforated doors.
v Plan the device installation starting from the bottom of the rack cabinet.
v Install the heaviest device in the bottom of the rack cabinet.
v Do not extend more than one device out of the rack cabinet at the same time.
v Remove the rack doors and side panels to provide easier access during
v Connect the file module to a properly grounded outlet.
v Do not overload the power outlet when you install multiple devices in the rack
v Install the file module in a rack that meets the following requirements:
16
Storwize V7000 Unified: Quick Installation Guide
airflow.
cabinet. To help prevent damage to file module components, always install a
blank filler panel to cover the open space and to help ensure proper air
circulation.
installation.
cabinet.
– Minimum depth of 70 mm (2.76 inch) between the front mounting flange and
inside of the front door.
– Minimum depth of 157 mm (6.18 inch) between the rear mounting flange and
inside of the rear door.