7.3.4 To install the outdoor unit

EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07
NOTICE
Level. Make sure the unit is level. Recommended:
Use 4 sets of M12 anchor bolts, nuts and washers. Provide at least 150 mm of free
space below the unit. Additionally, make sure the unit is positioned at least
100 mm above the maximum expected level of snow.
Anchor points
Pedestal
When installing on a pedestal, make sure that the discharge grille still can be put in
its safety position. See
4
safety
position" [
 81].
(mm)
a Make sure not to cover the drain hole in the bottom plate of the unit.
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.
800
"7.3.7 To remove the discharge grille, and put the grille in
7
Unit installation
|
(mm)
4× M12
Installer reference guide
77