To Connect The Space Cooling/Heating On/Off Output - Daikin EPRA10EAV3 Installer's Reference Manual

Table of Contents

Advertisement

9.3.9 To connect the space cooling/heating ON/OFF output

EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07
A
B
A
B
3 Fix the cable with cable ties to the cable tie mountings. General information,
see
"9.3.1 To connect the electrical wiring to the indoor
INFORMATION
Cooling is only applicable in case of reversible models.
Wires: (2)×0.75 mm²
Maximum load: 0.3 A, 230 V AC
Maximum load: 1 A, 5 V DC
1 Open the following (see
1 User interface panel
2 Switch box
3 Switch box cover
4 Top cover
2 Connect the space cooling/heating ON/OFF output cable to the appropriate
terminals as shown in the illustration below.
1 2
X 2M
1
"7.2.6 To open the indoor
9
Electrical installation
|
2
1
N/- L/+
Alarm output
Max. load
0,3 A - 230 V AC
1 A - 5 V DC
4
unit" [
 117].
4
unit" [
 73]):
Installer reference guide
4
3
2
1
129

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents