13.3 Yearly maintenance

13.3.1 Yearly maintenance outdoor unit: overview

13.3.2 Yearly maintenance outdoor unit: instructions

13.3.3 Yearly maintenance indoor unit: overview

13.3.4 Yearly maintenance indoor unit: instructions

EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07
Check the following at least once a year:
Heat exchanger
Water filter
Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt,
leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked heat
exchanger can lead to too low pressure or too high pressure leading to worse
performance.
Water filter
Close the valve. Clean and rinse the water filter.
NOTICE
Handle the filter with care. To prevent damage to the mesh of the filter, do NOT use
excessive force when you reinsert it.
2
1
3
DANGER: RISK OF BURNING/SCALDING
The water in the storage tank and all the connected piping can be very hot.
Water pressure
Magnetic filter/dirt separator
Water pressure relief valve
Relief valve hose
Switch box
Storage tank water level
Water pressure – Space heating/cooling circuit
Keep water pressure above 1 bar. If it is lower, add water.
13
Maintenance and service
|
Installer reference guide
247