Location 244 Programming The Various Reader Timers; Location 245 Resetting The Reader Address; Location 246 Programming The Access Options - Interlogix NetworX NX-1701E Installation Manual

Proximity card reader
Table of Contents

Advertisement

Location 244 Programming the Various Reader Timers

(4 segment of numerical data)
Segment 1
Scan Time
Enter the amount of time required to hold a card between beeps to activate the functions programmed in Location 0,
Segments 2 and 3. This timer is timed in 1/100-second increments from 0 to 2.55 seconds. (Default is 100 = 1 second).
Segment 2
Relay Active Time
Enter the amount of time the onboard open collector output is energized once activated. This timer is timed in 1-
second increments from 0 to 255 seconds. (Default is 10 = 10 seconds).
Segment 3
Door Fault Warning Time
Enter the amount of time a monitored zone (see Location 243, Segment 1) must be faulted before sounding a warning
(local buzzer). The door fault warning is timed in 1-second increments from 0 to 255 seconds. (Default is 30 = 30
seconds).
Segment 4
Door Fault Alarm Time
Enter the amount of time a monitored zone (see Location 243, Segment 1) must be faulted before sending an alarm
condition to the control panel. The door fault alarm is timed in 1-second increments from 0 to 255 seconds. (Default is
0 = 0 seconds).

Location 245 Resetting the Reader Address

(1 segment of numerical data) If it is necessary to reset the address of the reader, enter a 0 in this location.
This will cause the reader to cease functioning. If a card is scanned with the system in Program
Mode, the reader will again find an available address and set itself, beeping back to the user the
address that was found as per the table on page 5. If the system is not in Program Mode and a card is
scanned at a reader with a reset address, then it will sound an error beep.

Location 246 Programming the Access Options

(2 segments of binary data)
Segment 1
Door Options
"On" if locking mechanism is a Maglock or Drop Bolt.
LED1 -
"On" if access is allowed regardless of Armed status of the system.
LED2 -
"On" if the door is not to be latched unlocked during an open schedule.
LED3 -
"On" if onboard open collector output only triggers during an open schedule.
LED4 -
"On" if onboard open collector output only triggers during a close schedule.
LED5 -
"On" if Forced Entry Alarm is logged.
LED6 -
"On" if access allowed without an RTE.
LED7 -
"On" if relay operates normally during off-schedule (outside of regular operating hours)
LED8 -
Segment 2
Enabling the Schedules for the Onboard Open Collector Output:
"On" if driver follows Schedule 1.
LED1 -
"On" if driver follows Schedule 2.
LED2 -
"On" if driver follows Schedule 3.
LED3 -
"On" if driver follows Schedule 4.
LED4 -
"On" if driver follows Schedule 5.
LED5 -
"On" if driver follows Schedule 6.
LED6 -
"On" if driver follows Schedule 7.
LED7 -
"On" if driver follows Schedule 8.
LED8 -
NX-1701E Installation manual
Page 13
31/01/05