Segment 2
LED1 (Green) Options:
LED1 -
"On" to follow Ready status of system. (Default is "On")
LED2 -
"On" to toggle with the open collector output activation. (Default is "On")
LED3 -
"On" if inverted.
LED4-8
Reserved.
Segment 3
LED2 (Red) Options:
LED1 -
"On" to follow Armed status of system. (Default is "On")
LED2 -
"On" to toggle with the open collector output activation.
LED3 -
"On" if inverted.
LED4-8
Reserved.
Segment 4
Reader Partition:
LED1 -
"On" if reader is in Partition 1. (Default is "On")
LED2 -
"On" if reader is in Partition 2. (Default is "On")
LED3 -
"On" if reader is in Partition 3. (Default is "On")
LED4 -
"On" if reader is in Partition 4. (Default is "On")
LED5 -
"On" if reader is in Partition 5. (Default is "On")
LED6 -
"On" if reader is in Partition 6. (Default is "On")
LED7 -
"On" if reader is in Partition 7. (Default is "On")
LED8 -
"On" if reader is in Partition 8. (Default is "On")
L
243
OCATION
(2 segments of numerical data)
Segment 1
Door Shunt Zone
Program the zone that will be monitored as a door for access control. This location must be programmed with a valid zone for
monitored access control functions to work properly. (Default is 0)
 Additionally, this zone must be configured in the control panel as a Door Shunt zone by programming an unused Zone
Type Characteristic in locations 111-169 (Seg 4, Opt 4).
Segment 2
Request To Exit (RTE) Zone
Program the zone that will be monitored to signal an RTE. If this segment is programmed with a valid zone and the zone is faulted,
the reader will activate its onboard open collector output and send the RTE. (Default is 0)
Additionally, this zone must be configured in the control panel as an RTE zone by programming an unused Zone Type
Characteristic in locations 111-169 (Seg 4, Opt 3).
L
244
OCATION
(4 segment of numerical data)
Segment 1
Scan Time
Enter the amount of time required to hold a card between beeps to activate the functions programmed in Location 0, Segments 2 and
3. This timer is timed in 1/100-second increments from 0 to 2.55 seconds. (Default is 100 = 1 second).
Segment 2
Relay Active Time
Enter the amount of time the onboard open collector output is energized once activated. This timer is timed in 1-second increments
from 0 to 255 seconds. (Default is 10 = 10 seconds).
Segment 3
Door Fault Warning Time
Enter the amount of time a monitored zone (see Location 243, Segment 1) must be faulted before sounding a warning (local
buzzer). The door fault warning is timed in 1-second increments from 0 to 255 seconds. (Default is 30 = 30 seconds).
Segment 4
Door Fault Alarm Time
Enter the amount of time a monitored zone (see Location 243, Segment 1) must be faulted before sending an alarm condition to the
control panel. The door fault alarm is timed in 1-second increments from 0 to 255 seconds. (Default is 0 = disabled).
L
245
OCATION
(1 segment of numerical data) If it is necessary to reset the address of the reader, enter a 0 in this location.
This will cause the reader to cease functioning. If a card is scanned with the system in Program Mode, the reader
will again find an available address and set itself, beeping back to the user the address that was found as per the table
on page 3. If the system is not in Program Mode and a card is scanned at a reader with a reset address, then it will
sound an error beep.
L
246
OCATION
(2 segments of binary data)
Segment 1
Door Options
LED1 -
"On" if locking mechanism is a Maglock or Drop Bolt.
LED2 -
"On" if access is allowed regardless of Armed status of the system.