VANTAGE 549
aUXiliarY power operation
Start the engine and set the IDLER control switch to the desired
operating mode. Full power is available regardless of the welding
control settings, if no welding current is being drawn.
The auxiliary power of the VANTAGE® 549 consists of two 20
Amp-120VAC single phase (5-20R) GFCI duplex receptacles, one
50 Amp-120/240VAC single phase (14-50R) receptacle and one
50 Amp 240VAC three phase (15-50R) receptacle. The
120/240VAC receptacle can be split for single phase 120 VAC
operation.
The auxiliary power capacity is 11,000 watts of 60 Hz, single
phase power or 19,000 watts of 60Hz, three phase power. The
auxiliary power capacity rating in watts is equivalent to volt-
amperes at unity power factor. The maximum permissible current
of the 240 VAC output is 50 A. The 240 VAC single phase output
can be split to provide two separate 120 VAC outputs with a
maximum permissible current of 50 A per output to two separate
120 VAC branch circuits. Output voltage is within ± 10% at all
loads up to rated capacity.
NOTE: The two 120V GFCI receptacles and the two 120V circuits
of the 120/240V receptacle are connected to different phases and
cannot be paralleled.
The auxiliary power receptacles should only be used with three
wire grounded type plugs or approved double insulated tools with
two wire plugs.
The current rating of any plug used with the system must be at
least equal to the current capacity of the associated receptacle.
TABLE B.5 VANTAGE® 549 DEUTZ SIMULTANEOUS WELDING AND POWER LOADS
WELD
AMPS
WATTS
0
100
11,000
PLUS
200
11,000
250
11,000
300
400
up to 575
TABLE B.6 VANTAGE® 549 DEUTZ Extension Cord Length Recommendations
Current
Voltage
Load
(Amps)
(Volts)
(Watts)
15
120
1800
15
240
3600
20
120
2400
20
240
4800
25
240
6000
30
240
7200
38
240
9000
50
240
11000
1 PHASE
AMPS
11,000
46
46
OR
46
46
9,400
39
4,600
19
0
0
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
30
(9)
40
(12)
60
(18)
75
(23)
30
(9)
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
siMUltaneoUs welDinG anD aUXiliarY power
loaDs
It must be noted that the above auxiliary power ratings are with no
welding load.
Simultaneous welding and power loads are specified in table B.5.
The permissible currents shown assume that current is being
drawn from either the 120 VAC or 240 VAC supply (not both at the
same time).
3 PHASE
WATTS
AMPS
19,000
46
16,600
40
13,400
32
OR
11,500
28
9,400
23
4,600
11
0
0
10 AWG
8 AWG
75
(23)
125
150
(46)
225
50
(15)
88
100
(30)
175
90
(27)
150
75
(23)
120
100
B-14
BOTH 1 AND 3 PHASE
WATTS
AMPS
------
46
------
46
------
46
11,000
------
9,400
------
4,600
------
0
0
6 AWG
(38)
175
(53)
300
(69)
350
(107)
600
(27)
138
(42)
225
(53)
275
(84)
450
(46)
225
(69)
250
(37)
175
(53)
300
(30)
150
(46)
250
125
(38)
200
OPERATION
4 AWG
(91)
(183)
(69)
(137)
(76)
(91)
(76)
(61)