Johnson Controls 300 Series Manual page 82

Network control module
Table of Contents

Advertisement

82
Network Control Module 300 Series Technical Bulletin
Making the N1 LAN Connection
Follow the steps below to connect the Fire-Net NCM to the N1 LAN.
1.
Install a T-connector into the port of the Fire-Net NCM N1 LAN
ARCNET board.
2.
Connect the N1 LAN cable to one end of the T-connector. If the
NCM is at the end of line, connect a 93-ohm terminator cap to the
other end of the T-connector. If the Fire-Net NCM is not at the
end of line, connect the other segment of N1 LAN cable (that goes
to the next N1 node) to the T-connector.
Refer to Figure 7 in the NCM Cable Guidelines, NCM N1 LAN
Connection section of this document. If you have not set the Fire-Net
NCM node number, see the Interface Boards, Installing the MIB-OWS
Board section of this appendix for details.
Making the MIFN Connection: Copper Wire
If you have not already installed the MIB-OWS board, see the
Interface Boards, Installing the MIB-OWS Board section in this
appendix to install it now. Once the board is installed, follow the steps
below.
To make the MIFN connection using copper wire:
1. Install each end of the twisted pair wire into the terminal block of
the MIB-OWS board, starting at the far left (Figure 28 and
Figure 29).
Note:
If the Fire-Net NCM is at the end of line, use the first
two terminals from the left. If the Fire-Net NCM is not at the end of
line, connect the twisted pair that goes to the next MIFN node into the
next two terminals.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ncm300Ncm311Ncm350Ncm350-8Ncm361Ncm361-8

Table of Contents