Detailed Procedures
Replacing an NCM401 with an NCM300
Network Control Module 300 Series Technical Bulletin
If objects have been added online, they are lost if the NC file is
recompiled. To avoid losing these objects, first perform an NC upload,
then a decompile (using UNDDL), and finally make the port changes
to the decompiled file.
To replace an NCM401 with an NCM300:
1. Remove any configured devices from Port 2 in the Global DDL
file.
2. Move the S2 trunk from Port 1 to Port 2 in the Global DDL file.
3. Specify 2 for the S2 trunk number parameter for migration devices
(DSC8500, FPU) in the NC file.
4. After recompiling the Global DDL and NC files, all GPL and
JC-BASIC processes must be translated.
55