4
Network Control Module 300 Series Technical Bulletin
Table 1: NCM300 Series NCMs
Model
NCM300
NCM311
NCM350
NCM350-8
NCM361
NCM361-8
Fire-Net NCM
Smoke Control NCM
Description
(NU-NCM300-0, -1) The NCM300 is connected to the Metasys network via the
N1 ARCNET® Local Area Network (LAN).
(NU-NCM311-1) The NCM311 is the European version of the NCM300. Construction
and operation are similar to the NCM300; however, there are minor modifications that
are required to conform with European Safety and Emission standards that apply in all
European Union countries.
(NU-NCM350-1) The NCM350 is functionally the same as the NCM300; however, it
can connect to either an ARCNET or Ethernet LAN.
You can upgrade from an NCM300 either by swapping the NU-NCM300-0 for an
NCM350, or by upgrading an NU-NCM300-1 at Rev. B or later using the
NU-NCM300-1 to NU-NCM350-1 Upgrade Kit (NU-ROM150). Instructions come with
the upgrade kit.
Note:
Do not attempt to upgrade NU-NCM300-1s at Rev. A hardware or any
revisions of NU-NCM300-0s to NCM350s. If you have already tried to upgrade one of
these models, choose one of the following options:
Replace the ROM SIMM with an NU-ROM101. The NCM is now an NCM300 suitable
for ARCNET applications only.
Return the NCM to the repair center for upgrade to NU-NCM350-1. Go to the Products
Focus tab and click on Repair Center > NCM3n0Upgrade on The Advisor for details.
The physical difference between the NCM300 and the NCM350 is a Flash chip in
place of the ROM chip. This Flash chip contains everything that is in the ROM, along
with configuration data. The Flash chip also contains information about the ISA drivers,
and the user can download additional information to the Flash chip.
Updated version of the NCM350. Contains 8 MB total memory. Replaces all previous
versions of NCM300s and NCM350s. Meets UL 864 UUKL for smoke control
applications.
(NU-NCM361-1) The NCM361 is the European version of the NCM350. You can
purchase the NCM361 new, or you can upgrade an NCM311 either by swapping the
NU-NCM311-0 for an NCM361 or by upgrading the NU-NCM311-1 using the
NU-NCM311-1 to NU-NCM361-1 Upgrade Kit (NU-ROM150). Instructions come with
the upgrade kit.
Construction and operation are the same as the NCM350; however, there are minor
modifications that are required to conform with European Safety and Emission
standards that apply in all European Union countries.
Updated version of the NCM361. Contains 8 MB total memory. Replaces all previous
versions of NCM311s and NCM361s.
(NU-NCM300-FIRE/NU-NCMFIRE-1) The Fire-Net NCM is connected to the
Metasys Intelligent Fire Network. It is physically the same as the NCM300; however, it
is UL 864 UOJZ Listed for fire alarm use. The NCM300-FIRE comes with a
preinstalled ARCNET board, 2 MB additional memory, and a special power supply.
The NU-NCMFIRE-1 is the same as the NU-NCM300-FIRE, except that it has 8 MB of
memory. For information on the Fire-Net NCM, refer to the Metasys Intelligent Fire
Network Technical Bulletin (LIT-448196).
(NU-NCM300-2, replaced by NU-NCM350-8) The Smoke Control NCM is physically
similar to the NCM300; however, it is UL 864 UUKL Listed. For information on the
Smoke Control NCM, refer to the Smoke Control Technical Bulletin (LIT-636330).