Hoshizaki IM-50BAA-LM Service Manual page 29

Self-contained cuber
Hide thumbs Also See for IM-50BAA-LM:
Table of Contents

Advertisement

Control Board (CB) Setting Menu
Category No. Item
Water
10 Harvest Cycle Water Supply Time: Water
Supply
Temperature Lower Than 13°C
Time to supply harvesting water to melt ice on
water plate at water supply temp lower than 13°C.
Adjustable between 1 and 99 sec. When set to "99",
harvesting water keeps running until evaporator
(cube control) thermistor senses harvest termination
temp.
11 Harvest Cycle Water Supply Time: Water
Temperature 13°C or Higher
Time to supply harvesting water to melt ice on
water plate at water supply temp of 13°C or higher.
Adjustable between 1 and 99 sec. When set to "99",
harvesting water keeps running until evaporator
(cube control) thermistor senses harvest termination
temp.
12 Freeze Cycle Water Supply Time: Partial/Full Drain
Time to supply icemaking water depending on partial
or full drain flush.
13 Water Temperature Correction Value
Value added to correct the difference between
the temperature at the evaporator (cube control)
thermistor and actual water supply temperature.
14 Partial/Full Drain Flush Selection
Selection between full and partial drain flush
of icemaking water plate in case of cloudy ice
production even after hard water control. Icemaking
water supply time and water plate overflow pipe
direction need to be changed.
15 Freeze Cycle Water Supply Time
Time to supply additional icemaking water required
after pump motor starts following normal icemaking
water supply time.
16 Low Water Detection Time
Time to detect low water within which pump motor
starts and reaches the target rotation speed. The
longer set time becomes, the easier low water
detects. The shorter set time becomes, the harder
low water detects. No low water detection when set
to "0".
SETTING CHANGE IS INEFFECTIVE.
Range
1 to 99 sec,
99=continuous
(1 sec.
increments)
1 to 99 sec,
99=continuous
(1 sec.
increments)
0 to 90 sec.
(1 sec.
increments)
+0 to +20K
(1K increments)
Partial=1; Full=0
0 to 90 sec.
(1 sec.
increments)
0 to 90 sec.
0=no detection
(1 sec.
increments)
28
Default
Default
(50BAA-Q)
(50BAA-LM)
1
99
1
60
0
24
4
8
0
1
15
12
0
0