To Connect The Domestic Hot Water Pump - Daikin ERRA08-12EW1 Installer's Reference Manual

Table of Contents

Advertisement

9
|
Electrical installation

9.3.5 To connect the domestic hot water pump

Installer reference guide
142
B
A
B
4 Fix the cable with cable ties to the cable tie mountings.
Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A
(continuous)
[9.2.2] DHW pump
[9.2.3] DHW pump schedule
1 Open the service cover. See
2 Open the following (see
1 Top panel
2 User interface panel
3 Upper switch box cover
3 Connect the domestic hot water pump cable to the appropriate terminals as
shown in the illustration below.
A
3 4 5 6
X5M
"7.2.2 To open the outdoor
"7.2.6 To open the indoor
M M2P
1~
4
unit" [
 78].
4
unit" [
 81]):
1
3
2
ERRA08~12E + ELVH/X12S18+23E