To Connect The Space Cooling/Heating On/Off Output - Daikin ERRA08-12EW1 Installer's Reference Manual

Table of Contents

Advertisement

9
|
Electrical installation

9.3.7 To connect the space cooling/heating ON/OFF output

Installer reference guide
144
B
A
B
a Installation of EKRP1HBAA is required.
b Prewiring between X2M/7+9 and Q1L (= thermal protector backup heater). Do NOT
change.
4 Fix the cable with cable ties to the cable tie mountings.
INFORMATION
Cooling is only applicable in case of reversible models.
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
1 Open the service cover. See
2 Open the following (see
1 Top panel
2 User interface panel
3 Upper switch box cover
3 Connect the space cooling/heating ON/OFF output cable to the appropriate
terminals as shown in the illustration below.
2
1
X2M
7
9
A4P
Y2
YC
7
9
X2M
b
"7.2.2 To open the outdoor
"7.2.6 To open the indoor
1+2
Wires connected to the space
cooling/heating ON/OFF output
3
Wire between X2M and A4P
A4P
Installation of EKRP1HBAA is
3
required.
A4P
a
4
unit" [
 78].
4
unit" [
 81]):
1
ERRA08~12E + ELVH/X12S18+23E
Daikin Altherma 3 R MT F
4P708474-1 – 2023.05
3
2