Error Messages and Remedies

Error messages
HEAD IS NOT
The Sensor Head is not connected cor-
CONNECTED
rectly.
NEIGHBOR UNIT
The Amplifier Units are not coupled cor-
IS NOT CON-
rectly.
NECTED
SYSTEM ERROR
Failed to configure FPGA.
ERROR CODE ??
Failed to initialize LCD.
Failed to recognize Amplifier Unit.
Failed to load data from flash memory.
Faulty hardware operation
Faulty software operation
TEACHING
The workpiece is not projected correctly.
FAILED
The teaching area is not set at the appro-
priate position.
In the following instances, error messages are not displayed, but the ERROR signal turns
ON.
Cause
TRIG was input while ENABLE was OFF.
Failed to teach from external device.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Error Messages and Remedies

Cause
Make sure that the Sensor Head is
connected correctly.
Make sure that the Amplifier Units are
connected correctly.
Faulty Amplifier Unit
Contact your OMRON representative.
Set the area so that the workpiece is
projected in the field-of-view.
Make sure that the appropriate teach-
ing area is set.
Countermeasure
Wait until ENABLE is turned ON and then input TRIG.
Set the area so that the workpiece is projected in the field-
of-view.
Make sure that the appropriate teaching area is set.
Make sure that TRIG timing is appropriate in the workpiece
move teaching mode.
Section 4
Countermeasure
Pages
p.38
p.27
-
p.38
p.49
Pages
p.34
p.38
p.49
p.34
ZFV
User's Manual
79