Endress+Hauser Proline Prowirl O 200 Brief Operating Instructions
Endress+Hauser Proline Prowirl O 200 Brief Operating Instructions

Endress+Hauser Proline Prowirl O 200 Brief Operating Instructions

Vortex flowmeter

Advertisement

Quick Links

KA01137D/06/EN/06.17
71359662
Products
Brief Operating Instructions
Proline Prowirl O 200
Vortex flowmeter
These Instructions are Brief Operating Instructions; they are
not a substitute for the Operating Instructions pertaining to
the device.
Detailed information about the device can be found in the
Operating Instructions and the other documentation:
• On the CD-ROM supplied (not included in the delivery for all
device versions).
• Available for all device versions via:
– Internet:
www.endress.com/deviceviewer
– Smart phone/tablet: Endress+Hauser Operations App
Solutions
Services

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Prowirl O 200

  • Page 1 Detailed information about the device can be found in the Operating Instructions and the other documentation: • On the CD-ROM supplied (not included in the delivery for all device versions). • Available for all device versions via: – Internet: www.endress.com/deviceviewer – Smart phone/tablet: Endress+Hauser Operations App...
  • Page 2 Proline Prowirl O 200 Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3: Table Of Contents

    12.3 Endress+Hauser services ........
  • Page 4: Document Information

    Document information Proline Prowirl O 200 Document information Symbols used 1.1.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in WARNING serious or fatal injury.
  • Page 5: Basic Safety Instructions

    Proline Prowirl O 200 Basic safety instructions 1.1.4 Symbols for certain types of information Symbol Meaning Symbol Meaning Permitted Preferred Procedures, processes or actions that Procedures, processes or actions that are permitted. are preferred. Forbidden Procedures, processes or actions that Indicates additional information.
  • Page 6: Designated Use

    Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
  • Page 7: Operational Safety

    It meets general safety standards and legal requirements. It also complies with the EC directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions.
  • Page 8: Incoming Acceptance And Product Identification

    (depends on device version) and documents present? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • Depending on the device version, the CD-ROM might not be part of the delivery! The Technical Documentation is available via the Internet or via the Endress+Hauser Operations App.
  • Page 9: Product Identification

    • Enter serial numbers from nameplates in W@M Device Viewer (www.endress.com/deviceviewer): All information about the measuring device is displayed. • Enter the serial number from the nameplates into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser Operations App: all the information for the measuring device is displayed.
  • Page 10 Storage and transport Proline Prowirl O 200 A0015604 Do not remove protective covers or caps installed on process connections. They prevent mechanical damage to the sealing surfaces and contamination in the measuring tube. 5.2.1 Measuring devices without lifting lugs WARNING Center of gravity of the measuring device is higher than the suspension points of the webbing slings.
  • Page 11: Installation

    Proline Prowirl O 200 Installation Installation Installation conditions 6.1.1 Mounting position Mounting location A0015543 Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction. Vortex meters require a fully developed flow profile as a prerequisite for correct volume flow measurement.
  • Page 12 Installation Proline Prowirl O 200 Orientation Compact version Remote version 4) 5) C Horizontal orientation, transmitter head down   A0015590 D Horizontal orientation, transmitter head at side   A0015592 In the case of liquids, there should be upward flow in vertical pipes to avoid partial pipe filling (Fig. A). Disruption in flow measurement! In the case of vertical orientation and downward flowing liquid, the pipe always needs to be completely filled to ensure correct liquid flow measurement.
  • Page 13 Proline Prowirl O 200 Installation Inlet and outlet runs To attain the specified level of accuracy of the measuring device, the inlet and outlet runs mentioned below must be maintained at the very minimum. Endress+Hauser...
  • Page 14 Installation Proline Prowirl O 200 15 × DN 5 × DN 20 × DN 5 × DN 25 × DN 5 × DN 5 × DN 40 × DN 17 × DN + 8 × h 5 × DN 20 × DN 5 ×...
  • Page 15 If the required inlet runs cannot be observed, it is possible to install a specially designed flow conditioner which can be ordered from Endress+Hauser. The flow conditioner is fitted between two pipe flanges and centered by the mounting bolts. Generally this reduces the inlet run needed to 10 ×...
  • Page 16 Installation Proline Prowirl O 200 abs. = absolute For the dimensions of the flow conditioner, see the "Technical Information" document, "Mechanical construction" section Outlet runs when installing external devices If installing an external device, observe the specified distance. 3...5 x DN 4...8 x DN...
  • Page 17 Proline Prowirl O 200 Installation Ex i: –40 to +85 °C (–40 to +185 °F) Ex d: –40 to +85 °C (–40 to +185 °F) ATEX II1/2G Ex d, Ex ia: –40 to +85 °C (–40 to +185 °F) Local display –20 to +70 °C (–4 to +158 °F)
  • Page 18 Installation Proline Prowirl O 200 NOTICE Electronics overheating on account of thermal insulation! ‣ Observe the maximum permitted insulation height of the transmitter neck so that the transmitter head and/or the connection housing of the remote version is completely free.
  • Page 19: Mounting The Measuring Device

    Proline Prowirl O 200 Installation A0019209  3 Layout for delta heat measurement of saturated steam and water Prowirl Temperature sensor Heat exchanger Heat flow Weather protection cover Observe the following minimum head clearance: 222 mm (8.74 in) Mounting the measuring device 6.2.1...
  • Page 20 Installation Proline Prowirl O 200 6.2.3 Mounting the sensor WARNING Danger due to improper process sealing! ‣ Ensure that the inside diameters of the gaskets are greater than or equal to that of the process connections and piping. ‣ Ensure that the gaskets are clean and undamaged.
  • Page 21 Proline Prowirl O 200 Installation Wall mounting 19 (0.6) 80 (3.15) A0019864  4 Engineering unit mm (in) Post mounting 20…70 ( 0.79 to 2.75) SW 13 A0019862  5 Engineering unit mm (in) Post retainer kit for post mounting...
  • Page 22: Post-Installation Check

    Installation Proline Prowirl O 200 6.2.5 Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned. max. 350° 8 mm 8 mm A0013713 6.2.6 Turning the display module The display module can be turned to optimize display readability and operability.
  • Page 23 Proline Prowirl O 200 Installation Has the correct orientation for the sensor been selected →  11? • According to sensor type  • According to medium temperature • According to medium properties (outgassing, with entrained solids) Does the arrow on the sensor nameplate match the direction of flow of the fluid through the piping ...
  • Page 24: Electrical Connection

    Electrical connection Proline Prowirl O 200 Electrical connection The measuring device does not have an internal circuit breaker. For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
  • Page 25 Proline Prowirl O 200 Electrical connection PROFIBUS PA Twisted, shielded two-wire cable. Cable type A is recommended. For further information on planning and installing PROFIBUS PA networks see: • Operating Instructions "PROFIBUS DP/PA: Guidelines for planning and commissioning" (BA00034S) • PNO Directive 2.092 "PROFIBUS PA User and Installation Guideline"...
  • Page 26 Electrical connection Proline Prowirl O 200 7.1.3 Terminal assignment Transmitter Connection versions A0020738 A0020739 Maximum number of terminals Maximum number of terminals for order code for Terminals 1 to 6: "Accessory mounted", option NA "Overvoltage Without integrated overvoltage protection protection"...
  • Page 27 Proline Prowirl O 200 Electrical connection Remote version In the case of the remote version, the sensor and transmitter are mounted separately from one another and connected by a connecting cable. The sensor is connected via the connection housing while the transmitter is connected via the connection compartment of the wall holder unit.
  • Page 28 Electrical connection Proline Prowirl O 200 7.1.4 Pin assignment, device plug PROFIBUS PA Device plug for signal transmission (device side) Assignment Coding Plug/socket PROFIBUS PA + Plug Grounding PROFIBUS PA – Not assigned A0019021 FOUNDATION Fieldbus Device plug for signal transmission (device side)
  • Page 29 Proline Prowirl O 200 Electrical connection potential equalization, therefore, cable shielding of fieldbus systems should only be grounded on one side, for example at the fieldbus supply unit or at safety barriers. NOTICE In systems without potential matching, the multiple grounding of the cable shield causes mains frequency equalizing currents! Damage to the bus cable shield.
  • Page 30 Electrical connection Proline Prowirl O 200 7.1.6 Requirements for the supply unit Supply voltage Transmitter Increase in minimum terminal voltage Increase in minimum Local operation terminal voltage Order code for "Display; Operation", option C: + DC 1 V Local operation SD02 Order code for "Display;...
  • Page 31 Proline Prowirl O 200 Electrical connection R [ ] U [V] A0020417  7 Load for a compact version without local operation Operating range 1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/ switch output"...
  • Page 32: Connecting The Measuring Device

    Electrical connection Proline Prowirl O 200 Connecting the measuring device NOTICE Limitation of electrical safety due to incorrect connection! ‣ For use in potentially explosive atmospheres, observe the information in the device-specific Ex documentation. 7.2.1 Connecting the remote version WARNING Risk of damaging the electronic components! ‣...
  • Page 33 Proline Prowirl O 200 Electrical connection Connecting the sensor connection housing 3 mm A0020410 A0020411 NOTICE Terminals tightened with an incorrect tightening torque. Incorrect connection or damaged terminal. ‣ Tighten the terminals with a tightening torque in the 1.2 to 1.7 Nm range.
  • Page 34 Electrical connection Proline Prowirl O 200 Connection to the wall holder of the transmitter Connecting the transmitter via plug A0020412 Connecting the transmitter via terminals 3 mm A0020404 Endress+Hauser...
  • Page 35 Proline Prowirl O 200 Electrical connection TX 10 8 mm A0020405 ~15° A0020406 Endress+Hauser...
  • Page 36 Electrical connection Proline Prowirl O 200 A0020407 A0020409 Wire the connecting cable:  Terminal 1 = brown cable Terminal 2 = white cable Terminal 3 = yellow cable Terminal 4 = green cable Connect the cable shield via the cable strain relief.
  • Page 37 Proline Prowirl O 200 Electrical connection Connection via terminals 3 mm 20 mm 10 (0.4) mm (in) A0013836 ‣ Connect the cable in accordance with the terminal assignment . For HART communication: when connecting the cable shielding to the ground terminal, observe the grounding concept of the facility.
  • Page 38: Hardware Settings

    Electrical connection Proline Prowirl O 200 7.2.3 Ensuring potential equalization Requirements Please consider the following to ensure correct measurement: • Same electrical potential for the fluid and sensor • Remote version: same electrical potential for the sensor and transmitter • Company-internal grounding concepts •...
  • Page 39: Ensuring The Degree Of Protection

    Proline Prowirl O 200 Electrical connection 2 + 8 = 10 A0015902  9 Example of hardware addressing; switch 8 is set to the "OFF" position; switches 1 to 7 define the address. Software addressing Set switch 8 to "ON".
  • Page 40: Post-Connection Check

    Electrical connection Proline Prowirl O 200 To ensure that moisture does not enter the cable entry, route the cable so that it loops down before the cable entry ("water trap").  A0013960 Insert dummy plugs into unused cable entries. Post-connection check Are cables or the device undamaged (visual inspection)? ...
  • Page 41: Operation Options

    Proline Prowirl O 200 Operation options Operation options Structure and function of the operating menu 8.1.1 Structure of the operating menu Operating menu for operators and maintenances Language Operation task-oriented Setup Diagnostics Operating menu for experts Expert function-oriented A0014058-EN  11 Schematic structure of the operating menu 8.1.2...
  • Page 42: Access To The Operating Menu Via The Local Display

    Operation options Proline Prowirl O 200 Access to the operating menu via the local display X X X X X X 19.184 mA 12.5 X X X X X X Language 20.50 Ã English Deutsch Español Français User ABC_ DEFG...
  • Page 43 Proline Prowirl O 200 Operation options 8.2.1 Operational display Status area The following symbols appear in the status area of the operational display at the top right: • Status signals – F: Failure – C: Function check – S: Out of specification –...
  • Page 44 Operation options Proline Prowirl O 200 Display area • Icons for menus – : Operation – : Setup – : Diagnostics – : Expert • : Submenus • : Wizards • : Parameters within a wizard • : Parameter locked 8.2.3...
  • Page 45 Proline Prowirl O 200 Operation options 8.2.4 Operating elements Keys and meaning Minus key • In a menu, submenu: Moves the selection bar upwards in a choose list. • With a wizard: Confirms the parameter value and goes to the previous parameter.
  • Page 46: Access To The Operating Menu Via The Operating Tool

    Operation options Proline Prowirl O 200 8.2.5 Further information For further information on the following topics, see the Operating Instructions for the device • Calling up help text • User roles and related access authorization • Disabling write protection via access code •...
  • Page 47 Proline Prowirl O 200 Operation options Via PROFIBUS PA network This communication interface is available in device versions with PROFIBUS PA. A0019013  13 Options for remote operation via PROFIBUS PA network Automation system Segment coupler PROFIBUS DP/PA Computer with PROFIBUS network card...
  • Page 48 FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field devices in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition.
  • Page 49 Proline Prowirl O 200 Operation options Establishing a connection For additional information, see Operating Instructions BA00027S and BA00059S User interface Xxxxxx/…/…/ Device name: kg/h Xxxxxxx Mass flow: 12.34 Device tag: Xxxxxxx Volume flow: 12.34 m /h ³ Status: Good Xxxxxx...
  • Page 50: System Integration

    System integration Proline Prowirl O 200 System integration For detailed information on system integration, see the Operating Instructions for the device. Commissioning 10.1 Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed.
  • Page 51: Configuring The Measuring Device

    Proline Prowirl O 200 Commissioning X X X X X X X 20.50 Main menu 0104-1 Language English Operation Setup Language 0104-1 English à Deutsch Español Français Language 0104-1 à English Deutsch Español Français Hauptmenü 0104-1 Sprache Deutsch Betrieb Setup A0013996 ...
  • Page 52: Defining The Tag Name

    Diagnostic information Proline Prowirl O 200 Wizard Meaning Display Configure the measured value display Output conditioning Define the output conditioning Low flow cut off Set the low flow cut off 10.5 Defining the tag name To enable fast identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting.
  • Page 53 Proline Prowirl O 200 Diagnostic information X X X X X X X X X X X X X X 20.50 S801 Supply voltage Menu Diagnostic list Diagnostics 1 S801 Supply voltage Diagnostics 2 Diagnostics 3 Supply voltage (ID:203) S801 0d00h02m25s...
  • Page 54: General Troubleshooting

    Diagnostic information Proline Prowirl O 200 11.1 General troubleshooting For local display Problem Possible causes Remedy Local display dark and no output Supply voltage does not match the Apply the correct supply voltage . signals value indicated on the nameplate.
  • Page 55: Maintenance

    Proline Prowirl O 200 Maintenance Problem Possible causes Remedy Device shows correct value on local Configuration error Check and correct the parameter display, but signal output is incorrect, configuration. though in the valid range. Device measures incorrectly. Configuration error or device is 1.
  • Page 56: Measuring And Test Equipment

    Endress+Hauser housing seals. 12.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. For a list of some of the measuring and test equipment, refer to the "Accessories" chapter of the "Technical Information"...
  • Page 60 www.addresses.endress.com...