5.3

Wiring rules

When wiring use cables with the following AWG categories or cross sections.
Wiring rules for ...
connectable cable cross sec‐
tions for flexible cables ...
Stripped length of the cable
Wire end ferrule according to DIN 46228 with plastic ferrule**
* AWG: American Wire Gauge
** See note "Wire end ferrules"
Note
Wire end ferrules
Use crimp shapes with smooth surfaces, such as provided by square and trapeze shaped crimp
cross sections.
Crimp shapes with wave-shaped profile are unsuitable.
5.4

Power supply

Notes on the power supply
Incorrect power supply
Never operate the device to alternating voltage.
Never operate the device with DC voltage higher than 32 VDC.
SCALANCE XF-200BA
Operating Instructions, 02/2023, C79000-G8976-C470-08
WARNING
without wire end ferrule
with wire end ferrule**
with TWIN wire end ferrule**
Connecting up
5.4 Power supply
Spring-loaded terminals
0.25 - 2.5 mm
2
AWG: 24 - 14
0.25 - 2.5 mm
2
AWG: 24 - 14
2 x 0.25 - 2 x 1 mm
2
AWG: 24 - 18
8 - 10 mm
8 - 10 mm