Lennox Allied Air Enterprise A97DSMV Installation Instructions Manual page 62

Warm air gas furnace downflow air discharge direct vent
Table of Contents

Advertisement

Code
Diagnostic Codes / Status of Equipment
E273
Soft lockout - Exceeded maximum number of
recycles. Last recycle due to flame failure
E274
Soft lockout - Exceeded maximum number of
recycles. Last recycle failed due to the limit circuit
opening or limit remained open longer than 3
minutes.
E275
Soft lockout - Flame sensed out of sequence.
Flame signal is gone.
E276
Soft lockout calibration failure.
E290
Ignitor circuit fault - Failed ignitor or triggering
circuitry.
E291
Heat airflow restricted below the minimum.
E292
Indoor blower motor unable to start due to
obstructed wheel seized bearings.
E294
Combustion air inducer over current.
E295
Indoor blower motor temperature is too high.
E310
Discharge error temperature sensor failure. Only
shown if shorted or out of range.
E311
Heat rate reduced to match indoor blower airflow.
Page 62 of 73
Action Required to Clear and Recover
Check micro-amperes of flame sensor using control
diagnostics or field installed mode. Clean or replace
sensor. Measure voltage of neutral to ground to ensure
good unit ground. Alert clears after current heat call has
been completed.
Shut down system 1-hour soft lockout. Check firing rate
and air flow. Check for blockage. Clears when heat call
finishes successfully.
Shut off gas. Check for gas valve leak. 1-hour soft
lockout. Clears when flame has been proven stable.
Unable to perform pressure switch calibration. Check
vent system and pressure switch wiring connections.
1-hour soft lockout. Clears when calibration has finished
successfully.
Measure resistance of hot surface igniter. Replace if
open or not within specifications. 1-hour soft lockout.
Clears when flame has been proven stable.
Check for dirty filter and airflow restriction. Check
blower performance. 1-hour soft lockout. Cleared when
heat call finishes successfully.
Indoor blower motor unable to start (seized bearing,
stuck wheel, etc.) Replace motor or wheel if assembly
does not operate or meet performance standards.
1-hour soft lockout. Clears after circulator successfully
starts.
Check combustion blower bearings wiring and
amps. Replace if does not operate or does not meet
performance standards. Clears after inducer current is
sensed to be in-range after the ignition following the soft
lockout or reset.
Indoor blower motor over temperature (motor tripped
on internal protector). Check motor bearings and amps.
Replace if necessary. Cleared after blower demand is
satisfied.
Compare discharge sensor resistance to temperature
resistance charts in installation instructions.. Replace
sensor if necessary. Cleared in Communicating
mode 30 seconds after fault recovered. In Non-
Communicating mode cleared after the current heat call
is completed.
Warning Only. Furnace blower in cutback mode due to
restricted airflow. Reduce firing rate every 60 seconds
to match available CFM. Check filter and duct system.
To clear replace filter if needed or repair/add duct.
2-stage controls will reduce firing rate to 1-stage. Clears
when heat call finished successfully.