Venting

Piping Suspension Guidelines
NOTE: Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
Figure 16.
If this gas furnace replaces a furnace which was commonly vented
with another gas appliance, the size of the existing vent pipe for that
gas appliance must be checked. Without the heat of the original
furnace flue products, the existing vent pipe is probably oversized
for the single water heater or other appliance. The vent should be
checked for proper draw with the remaining appliance.
Figure 17.
1.
In areas where piping penetrates joist or interior walls,
hole must be large enough to allow clearance on all
sides of pipe through center of hole using a hanger.
2.
When furnace is installed in a residence where unit
is shut down for an extended period of time, such
as a vacation home, make provisions for draining
condensate collection from trap and lines.
507029-05
Exhaust Piping
See Figure 19 and Figure 21
Route piping to outside of structure. Continue with
installation following instructions given in piping termination
section.
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical
discharge through an existing unused stack is required,
insert PVC pipe inside the stack until the end is even
with the top or outlet end of the metal stack.
The exhaust vent pipe operates under positive pressure
and must be completely sealed to prevent leakage of
combustion products into the living space.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
Vent Piping Guidelines
This unit is installed only as a Direct Vent gas central
furnace.
NOTE: In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing – Size pipe according to
Table 6 and Table 7A through Table 7B. Table 6 lists the
minimum vent pipe lengths permitted. Table 7A through
Table 7B list the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
it exits the termination. Refer to Table 7A through Table 7B.
In some applications which permit the use of several
different sizes of vent pipe, a combination vent pipe may
be used. Contact Allied Air Technical Service for more
information concerning sizing of vent systems which
include multiple pipe sizes.
Issue 2241
CAUTION
CAUTION
WARNING
Page 13 of 73