Figure 2.3 Quck Menu Icons; Figure 2.4 Local And Current Cool/Heat Setpoints - Bard MULTI-TEC W18AAPA Installation And Service Instructions Manual

Table of Contents

Advertisement

TEC-EYE
Menu Structure
TM
Quick Menu
Data Log
Unit Information
Setpoints
Main Menu
System Configuration
Advanced System Configuration
I/O Configuration
On/Off
Alarm Logs
Settings
Logout
In addition to the menu structure above, there are also
Status and Alarm screens.
TEC-EYE
Acronyms
TM
MAT – Mixed air temperature
RAT – Return air temperature
OAT – Outdoor air temperature
OAH – Outdoor air humidity
Blower – Indoor Blower Status
Damper – Free cooling damper position status
C1 – Compressor activate status
H1 – Heater Stage 1 status
H2 – Heater Stage 2 status
ODP – Calculated outdoor dew point
FC – Free cooling status
RN – Component run time in minutes in last hour
ST – Number of start requests in last hour
NOTE: Digital refers to On/Off whereas analog is a
variable input.
Status Screen
The Status screen is the default start-up screen and
also the return screen after 5 minutes of no activity.
The screen can be accessed any time by pressing the
BACK button repeatedly.
The wall-mount unit address is displayed in the upper
right corner on the Status screen (see Figure 2.1). The
Status screen also shows the current date, time, return
air temperature, mixed air temperature, outdoor air
temperature, outdoor humidity and outdoor dewpoint
conditions. Blower, damper and unit status are also
displayed.
The Quick Menu is accessible from the Status screen.
Data Log, Unit Information and Setpoints are available
through the Quick Menu. Pressing the UP or DOWN
keys while on the Status screen will change the Quick
Menu icon displayed (see Figure 2.3). Press the
ENTER key when the desired icon is displayed.
FIGURE 2.3
Quick Menu Icons
Data Log
Unit Information
Setpoints: Local Cool and Heat/Current Cool and Heat
If at any time the unit(s) loses communication with
the LC6000 controller, the unit(s) will go to stand
alone mode. Local cooling and heating setpoints only
apply to stand alone mode. The Current cooling and
heating setpoints are the setpoints for the on and off
differential points.
The LC6000 setpoints will determine the Current
cooling and heating setpoints when communicating.
The Local cooling and heating setpoints will determine
the Current cooling and heating setpoints when in
stand alone mode.
To change local cool and heat setpoints:
1. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints icon. Press
ENTER key.
2. Press ENTER key to scroll to the selected choice
(see Figure 2.4).
3. Press UP or DOWN key on desired value until value
displays correctly.
4. Press ENTER key to submit value and move to next
parameter.
5. Press BACK key until Main Menu screen is
displayed.
FIGURE 2.4
Local Cool/Heat and Current Cool/Heat Setpoints
Executing a Run Test
Execute a run test on each unit to verify the equipment
is functioning correctly.
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
Setpoints
Manual 2100-665A
Page
25 of 51

Advertisement

Table of Contents
loading

Table of Contents