Tec-Eye Acronyms; Main Status Screen; Quick Menu; Setpoints - Bard MEGA-TEC W180B Service Instructions Manual

Wall-mount air conditioner
Table of Contents

Advertisement

TABLE 1

TEC-EYE Menu Structure

Menu/Screen Structure

Quick Menu

Setpoints (Orphan Mode
Temperature Control)
Information
Alarm Log
Main Menu
System Config
Adv. Sys. Config
I/O Config
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Fan/Blowers
Manual EEV
On/Off
Alarm Logs
Settings
Date/Time
Initialization
Change Passwords
Logout
TABLE 2

LC6000/TEC-EYE Passwords (Defaults)

User
Technician
Engineer
Use UP or DOWN keys and ENTER key to enter password.
The passwords listed above are the default passwords.
End users can change these passwords if additional
security is desired.

TEC-EYE Acronyms

MAT – Mixed air temperature
RAT – Return air temperature
SAT – Supply air temperature
OAT – Outdoor air temperature
OAH – Outdoor air humidity
Blower – Indoor blower speed
Fan – Outdoor fan speed
Password Level
Damper – Free cooling
Required

Main Status Screen

The main Status screen is the default start-up screen
None
and also the return screen after 5 minutes of no
activity. The screen can be accessed at any time by
None
pressing the ESCAPE key repeatedly.
The wall-mount unit address is displayed in the upper
None
right corner on the main Status screen (see Figure 1).
The main Status screen also shows the current date,
return air temperature (RAT), outdoor air temperature
User
(OAT) and unit status. See Table 3 on page 8 for wall-
Technician
mount unit status messages.
The Quick Menu is accessible from the main Status
Technician
screen. Setpoints, Information and Alarm Log are
Technician
available through the Quick Menu. Pressing the UP or
DOWN keys while on the main Status screen will change
Technician
the Quick Menu icon displayed (see Figure 3). Press the
Technician
ENTER key when the desired icon is displayed.
Technician
Technician
Technician
User
User
--
Quick Menu
Technician

Setpoints

From this screen, the local unit heating and cooling
Technician
setpoints can be changed.
Varies
Once the supervisory controller is connected, cooling
--
and heating setpoints will be communicated and local
cooling and heating setpoints will be replaced with the
communicated cooling and heating setpoints.
If at any time the wall-mount unit(s) loses
communication with the LC6000 controller, the wall-
mount unit(s) will go into orphan mode and operate
2000
using the last communicated setpoints.
1313
To verify or change the wall-mount unit cooling and
heating setpoints in orphan mode:
9254
1. Connect the TEC-EYE diagnostic tool to the control
2. From the Status screen, press UP or DOWN key
3. Press ENTER key to scroll to the selected choice
4. Press UP or DOWN key on desired value until value
FIGURE 3
Quick Menu Icons
Alarm Log
Information
board located in the unit.
until Quick Menu displays Setpoints icon. Press
ENTER key.
(see Figure 4 on page 9).
displays correctly.
Setpoints
Manual
2100-749
Page
7 of 68