Screen
Menu Item
On Diff
OA Humid Set
Press DOWN Key
A5
Economizer
OA Dew Pt Set
On Diff
Dewpoint Delay
Press DOWN Key
A6
Unit Config
Damper Modulation
Mixed FC Set
Gain
Integral
Derivative
Press DOWN Key
A7
Alarm Config
Mixed Air Alarms
Diff Lo
Diff Hi
Del
Low Pressure Alarms
OAT
Diff
Del
LDel
Two Count Del
Press DOWN Key
A8
Alarm Config
Damper Alarms
Open Del
Close Del
Freeze Alarm
Low Temp
Reset Temp
Reset Del
Press DOWN Key
A9
Alarm Config
Air Flow Alarm
Range
Default Value
-999.9 to 999.9
5.0°F
0-100%
80%
-999.9 to 999.9
55.0°F
-999.9 to 999.9
5.0°F
0-32767
120 sec
-999.9 to 999.9
55.0°F
-999.9 to 999.9
20.0°F
0-65535
120 sec
0-65535
0 sec
-999.9 to 999.9
10
-999.9 to 999.9
5.0
0-32767
30 sec
-999.9 to 999.9
55.0°F
-999.9 to 999.9
5.0
0-32767
120 sec
0-32767
180 sec
0-32767
900 sec
20 sec
300 sec
33.0°F
55.0°F
300 sec
Description
Differential used by outdoor setpoint
Setpoint to limit economizer operation
Setpoint used to limit economizer
operation
Differential used by OA dewpoint
setpoint
Time delay used for dewpoint conditions
Descriptive text
Setpoint being used by economizer PID
Proportional gain used by PID
Integral time used by PID
Derivative time used by PID
Heading
Descriptive text
Low differential for alarm
High differential for alarm
Delay for alarm
Descriptive text
OAT setpoint for alarm
Differential for OAT setpoint
Delay used for alarm (OAT above
setpoint)
Delay used for alarm (OAT below
setpoint)
Delay before retry counter resets
Time delay before alarm occurs on fail
to open
Time delay before alarm occurs on fail
to close
Setpoint for freeze alarm
Temperature for auto reset of alarm
Time delay for auto reset of alarm
Manual 2100-665A
Page
47 of 51