Chase Enclosure - Regency City CV60EPV-NG Owners & Installation Manual

Direct vent
Table of Contents

Advertisement

Chase Enclosure

Opening for vent
When choosing to install the ventilation openings from the front or both sides, The top of the ventilation opening cannot be any lower than 0-2" (51mm)
4"-4.5"
from the top of the chase enclosure for all installations.
Minimum height of enclosure from base of appliance is 81-1/4" (2064mm).
(102 mm x 114 mm)
A minimum 180in
opening in the enclosure is required to maintain safe operating temperatures. This can be achieved in a number of ways including the
2
examples shown in this manual.
IMPORTANT:
Exterior wall/Alcove enclosure: When installing into an exterior cavity or alcove enclosure (ceiling, back and sides), regardless of where appliance is
placed within the home, requires the use of either drywall or other means such as plywood, wood studs, etc. to prevent heat from escaping anywhere above
/through the enclosure other than the required grill / ventilation opening.
Internal chase: When installing as an internal chase framing installation ,regardless of where appliance is placed within the home, requires the use of either
drywall or other means such as plywood, on the rear wall of the chase to eliminate heat escaping into the rear wall cavity. If the chase is extended to the
ceiling ,the ceiling will also need to be finished in a manner to prevent heat escaping into floor joist/attic space.
One of the following methods must be used to prevent the heat from escaping.
a. If choosing drywall, ensure that the drywall is butt up tight with no gaps.
b. Plywood, wood studs, etc. installed tightly with no gaps.
As this appliance has been designed with all hot air escaping through the chase enclosure ventilation/grill openings only, if hot air is trapped as a result of
the hot air escaping through joints, crevasses, open studs, or other openings within the enclosure above, this will change the clearances within the enclosure
causing the enclosure to overheat. It is vital that all the hot air from within the enclosure exits through the ventilation openings only.
Ensure that the ventilation openings are made as such to prevent debris, objects from falling into the enclosure.
Warning: DO NOT cover or place objects in front of the ventilation opening air outlet(s).
Max. 2''
Max 3"
Stud
(51mm)
(76 mm)
Stud
Min 42.25" (1073 mm)
Top of chase enclosure
Ceiling
Minimum 180sq. inch opening
40" (1016 mm) Chase Vent
Top of chase enclosure
Top of chase enclosure
Max. 2''
Max 3"
(51mm)
(76 mm)
Stud
In the example above, the ceiling does not
meet the requirement as it is higher than
the specified minimum.
Top of chase enclosure is sealed off to
meet the 0-2'' (51mm) requirement.
installation
Ceiling
Minimum 180sq. inch opening
40" (1016 mm) Chase Vent
City Series CV60E-1 |
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

City cv60e-1City seriesCity cv60e-ng

Table of Contents