Wiring Instructions And Mounting Bracket Installation - Kidde P4010ACSAQ-WF User Manual

Smoke alarm with indoor air quality monitor
Hide thumbs Also See for P4010ACSAQ-WF:
Table of Contents

Advertisement

9. Wiring Instructions and Mounting Bracket Installation

For best Wi-Fi enrollment results, follow these steps:
1. Scan QR code shown in STEP 1 on the front of the Quick Start Guide. Install the Kidde app.
2. Open the Kidde app. Create and login to your account. Tap "Add a device." Select " Smoke Alarm with Indoor Air
Quality Monitor." Follow in-app steps.
3. Scan your unique QR code, shown in STEP 3 of the Quick Start Guide, or on back of your alarm. Setup and
connect alarm to the app. This will include the wiring and installation steps shown in sections 9, 10, and 11.
4. Complete setup by following in-app steps.
noTe: wi-Fi features do not function without AC power.
wiring requirements
• This alarm should be installed on a UL Listed or recognized junction box. All connections should be made by a
qualified electrician and all wiring used shall be in accordance with articles 210 and 300.3(B) of the U.S. National
Electrical Code ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdiction in your area. The multiple station
interconnect wiring to the alarms must be run in the same raceway or cable as the AC power wiring. In addition, the
resistance of the interconnect wiring shall be a maximum of 10 ohms.
• The appropriate power source is 120 Volt AC Single Phase, supplied from a non-switchable circuit.
• Smoke alarms are not to be used with detector guards unless the combination (alarm and detector guard) has been
evaluated and found suitable for that purpose.
• Kidde alarms are not designed, agency tested or certified for recessed mounting and should not be installed in
this manner. Recessed mounting impedes smoke entry into the smoke chamber, which may prevent the alarm
from sounding in a timely manner. This could endanger the lives of occupants in the residence. Kidde alarms are
designed, tested and certified for wall (if applicable) and ceiling surface mount only.
wArnInG: THe AlArM CAnnoT Be oPerATed FroM Power derIVed FroM A SQUAre wAVe,
ModIFIed SQUAre wAVe or ModIFIed SIne wAVe, InVerTer. THeSe TYPeS oF InVerTerS Are SoMe-
TIMeS USed To SUPPlY Power To THe STrUCTUre In oFF GrId InSTAllATIonS, SUCH AS SolAr or
wInd derIVed Power SoUrCeS. THeSe Power SoUrCeS ProdUCe HIGH PeAK VolTAGeS THAT wIll
dAMAGe THe AlArM.
wiring Instructions for AC Quick Connect Harness
CAUTIon: Turn off the main power to the circuit before wiring the AC Quick Connect Harness.
• For alarms that are used as single station, DO NOT CONNECT THE RED WIRE TO ANYTHING. Leave the red wire
insulating cap in place to make certain that the red wire cannot contact any metal parts or the electrical box.
noTe: Single station alarms (including this Wi-Fi model, if used as a single station alarm) CANNOT send or receive smoke
or CO alarm signals to other hardwire interconnect alarms in your home. If this model is used as a single station alarm, it
will send notifications ONLY to your mobile device (after the wi-Fi alarm is registered with the Kidde app).
14

Advertisement

Table of Contents
loading

Table of Contents