Error Display - Siemens SIMATIC ET 200SP Manual

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Interrupts, error messages, diagnostics and system alarms
5.2 Interrupts

Error display

Table 5- 5
Error type
(MAINT)
1
Note
The following LEDs indicate a short-circuit in the backplane bus supply or in the bus
connection supply:
• PWR LED: On
• RN, ER and MT LED: Off
5.2
Interrupts
Introduction
The I/O device triggers interrupts as a reaction to specific errors. Interrupts are evaluated
based on the I/O controller used.
Evaluating interrupts with I/O controllers
The ET 200SP distributed I/O system supports the following interrupts:
● Diagnostic error interrupts
● Hardware interrupts
● Pull/plug interrupts
In the event of an interrupt, interrupt OBs are automatically called in the CPU of the IO
controller.
Information on the cause and class of the error is already available, based on the OB
number and start information.
Detailed information on the error event can be obtained in the error OB using the instruction
"RALRM" (read additional interrupt information).
38
Error display
Error location
Cause of error
(ERROR/ MAINT)
65
No server module
Interruptions on the backplane bus
Short circuit of communication on
the backplane bus
IM 155-6 PN HF interface module (6ES7155-6AU00-0CN0)
Manual, 03/2015, A5E03915895-AF
Solution
Check the configuration
of the ET 200SP.