PROFINET IO with BusAdapter BA 2×RJ45
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×RJ45.
Table 3- 2
PROFINET IO with BusAdapter BA 2×FC
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×FC.
Table 3- 3
IM 155-6 PN HF interface module (6ES7155-6AU00-0CN0)
Manual, 03/2015, A5E03915895-AF
PROFINET IO pin assignment with BusAdapter BA 2×RJ45
View
1
2
3
4
5
6
7
8
PROFINET IO pin assignment with BusAdapter BA 2×FC
View
Signal name
TD
Transmit data +
TD_N
Transmit data –
RD
Receive data +
GND
Ground
GND
Ground
RD_N
Receive data –
GND
Ground
GND
Ground
Signal name
1
TD
2
TD_N
3
RD
4
RD_N
Wiring
3.1 Pin assignment
Description
Description
Transmit data +
Transmit data –
Receive data +
Receive data -